- Home
- Schneider Easy TeSys Contactors
- Schneider Electric LC1E3210BD Easy TeSys Control LC1E 32A 3P 400V 15kW Contactor Schneider Electric LC1E3210BD Easy TeSys Control LC1E 32A 3P 400V 15kW Contactor
Schneider Electric LC1E3210BD Easy TeSys Control LC1E 32A 3P 400V 15kW Contactor
Schneider Electric LC1E3210BD Easy TeSys Control LC1E 32A 3P 400V 15kW Contactor
Get Quote
- Description
The Schneider Electric LC1E3210BD is a 3-pole Easy TeSys Control contactor rated 32 A (AC-3) at up to 440 V AC, built for direct-on-line motor control up to 15 kW at 400 V. It carries a 24 V DC coil and one NO auxiliary contact, making it a compact DIN-rail or plate-mount switching device for control panels and motor starter combinations.
Technical Specifications
| Reference | LC1E3210BD |
| Brand | Schneider Electric |
| Range | Easy TeSys Control |
| Device short name | LC1E |
| Product type | Contactor |
| Poles | 3P (3 NO) |
| Rated operational current (Ie) AC-3 | 32 A at <=440 V AC |
| Rated operational current (Ie) AC-1 | 50 A at <=440 V AC |
| Motor power | 15 kW at 400 V AC |
| Control circuit voltage (Uc) | 24 V DC |
| Auxiliary contact composition | 1 NO |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Rated short-time withstand current (Icw) | 260 A / 10 s |
| Rated making capacity | 416 A at 440 V AC |
| Rated breaking capacity | 272 A at 440 V |
| Maximum operating rate | 1800 cyc/h at 60 C |
| Mounting support | DIN rail / plate |
| IP degree of protection | IP20 |
| Ambient operating temperature | -5...55 C |
| Dimensions (H x W x D) | 85 x 56 x 99 mm |
| Net weight | 0.55 kg |
Certifications & Standards
- CB Scheme
- CCC
- CE
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-4-1
- EN/IEC 60947-5-1
- GB/T 14048.1
- GB/T 14048.4
- GB/T 14048.5
Selection Notes
The 32 A AC-3 rating supports direct-on-line starting of motors up to 15 kW at 400 V AC, while the separate 50 A AC-1 rating applies only to resistive or heating loads, not motor circuits. A 24 V DC coil suits control panels standardized on low-voltage DC control power rather than mains-referenced AC coils. The single NO auxiliary contact provides one spare signal for a motor-running indication, interlock, or PLC feedback point without an add-on auxiliary contact block. The 260 A / 10 s short-time withstand current gives margin to ride through inrush conditions under coordinated fuse protection (63 A gG, type 1).