- Description
The Siemens 6EP3233-0TA00-0AY0 SITOP PSU3400 is a DC/DC converter that steps a 48 V DC (28-60 V range) input down to a stabilized 24 V DC output at 5 A, adjustable up to 6 A. It reaches 92% efficiency and fits a 32 mm DIN-rail footprint for battery- or 48 V-bus-fed control cabinets.
Technical Specifications
| SKU | 6EP3233-0TA00-0AY0 |
| Brand | Siemens |
| Series | SITOP PSU3400 |
| Product type designation | PSU3400 |
| Input voltage (DC) | 28-60 V (rated 48 V) |
| Input current at 48 V | 2.7 A |
| Output voltage | 24 V DC, adjustable 24-28 V via potentiometer |
| Output current, rated | 5 A (range 0-6 A) |
| Output power, typ. | 130 W |
| Efficiency | 92 % |
| Residual ripple, max. | 150 mV |
| Short-circuit protection | Electronic shutdown, automatic restart |
| Parallel operation | Up to 2 units for increased power |
| Degree of protection | IP20 |
| Operating temperature | -25…+70 °C |
| Mounting | DIN rail EN 60715 35x7.5/15 |
| Enclosure dimensions (W×H×D) | 32 × 100 × 100 mm |
| Net weight | 0.32 kg |
Certifications & Standards
- CE
- EAC
- RCM
- CB
- ABS
- DNV
Selection Notes
The 48 V DC input (28-60 V range) is what separates this PSU3400 unit from the AC-mains SITOP power supplies — choose it where the cabinet already runs a 48 V DC bus, such as a telecom-style battery system, rather than adding an AC feed. The output is adjustable 24-28 V via potentiometer, useful for compensating voltage drop on long 24 V DC runs instead of a fixed-output sibling. Two units can be connected in parallel to raise available current beyond the single-unit 5 A/6 A rating without moving to a higher-power PSU model.
Applications
48 V DC bus-fed control panels, telecom or battery-backed cabinets, and machine control needing a regulated 24 V feed from an intermediate 48 V rail.