- Home
- Redundancy, Selectivity & DC Converter Modules
- Siemens 6EP1961-2BA31 SITOP PSE200U Selectivity Module 4x3 A 24 V DC Siemens 6EP1961-2BA31 SITOP PSE200U Selectivity Module 4x3 A 24 V DC
Siemens 6EP1961-2BA31 SITOP PSE200U Selectivity Module 4x3 A 24 V DC
Siemens 6EP1961-2BA31 SITOP PSE200U Selectivity Module 4x3 A 24 V DC
Get Quote
- Description
The Siemens SITOP PSE200U 6EP1961-2BA31 is a 4-channel selectivity module that distributes a 24 V/12 A DC input across four individually monitored 3 A outputs, each with an adjustable overcurrent threshold from 0.5 to 3 A. It isolates a faulted branch within about 5 seconds on excess current while the other three channels stay powered, and reports per-channel status through a three-color LED.
Technical Specifications
| SKU | 6EP1961-2BA31 |
| Brand | Siemens |
| Series | SITOP PSE200U |
| Input Voltage | 24 V DC (22...30 V) |
| Input Current | 12 A rated |
| Number of Outputs | 4 |
| Output Current per Channel | 3 A rated |
| Adjustable Threshold | 0.5...3 A via potentiometer |
| Response Delay (overcurrent) | approx. 5 s maximum |
| Current Limitation Trip | 1.5x set value, typ. 100 ms |
| Immediate Switch-off | Iout above set value and Vin below 20 V, approx. 0.5 ms |
| Efficiency | 97% |
| Power Loss | 9 W typical |
| Protection Class | IP20, Class III |
| Ambient Temperature (operation) | -25...+60 degrees C, natural convection |
| Enclosure (W x H x D) | 72 x 80 x 72 mm |
| Net Weight | 0.2 kg |
| MTBF (40 degrees C) | 755,915 h |
Certifications & Standards
- CE
- UKCA
- EAC
- CB
- Shipbuilding
- ABS
- DNV
- EPD
Selection Notes
The PSE200U provides per-branch selectivity: a short circuit on one of the four 3 A outputs trips only that channel through its own current-dependent overload release, instead of pulling down the shared 12 A input bus. That makes it the right choice downstream of a single 24 V SITOP power supply feeding several independent I/O groups or field devices. Each channel's 0.5-3 A adjustable threshold can be tuned to the actual load current rather than left at the full 3 A rating, tightening fault detection, and the non-isolated remote reset input lets a channel be power-cycled without breaking the DIN-rail bus.
Applications
Distributing and protecting multiple 24 V field-device or I/O branch circuits from one power supply, selective fault isolation in control cabinets, and machine sub-circuit protection.