Siemens 6EP1961-2BA21 SITOP PSE200U 24V DC 4x10A Power Supply Selectivity Module
Siemens 6EP1961-2BA21 SITOP PSE200U 24V DC 4x10A Power Supply Selectivity Module
Get Quote
- Description
The Siemens 6EP1961-2BA21 SITOP PSE200U is a 4-channel selectivity module that splits a 24 V DC, 40 A input into four individually protected 10 A outputs with a current threshold adjustable from 3 to 10 A per channel. A common signaling contact reports overload status, and each channel switches off within about 5 seconds of exceeding its set threshold.
Technical Specifications
| SKU | 6EP1961-2BA21 |
| Brand | Siemens |
| Series | SITOP PSE200U |
| Product Type Designation | PSE200U |
| Input Voltage | 24V DC (22...30V) |
| Input Current, Rated | 40 A |
| Number of Outputs | 4 |
| Output Current per Channel | 10 A, up to 60 degrees C |
| Adjustable Threshold | 3 to 10 A via potentiometer |
| Response Delay, Max. | 5 s |
| Efficiency | 99% |
| Power Loss, Typ. | 10 W |
| Signaling Contact | Common changeover contact, 0.1A/24V DC |
| Enclosure Dimensions (WxHxD) | 72 x 80 x 72 mm |
| Protection Class | IP20 |
| MTBF at 40 degrees C | 540,979 h |
| Net Weight | 0.2 kg |
Certifications & Standards
- CE
- UKCA
- EAC
- CB
- ABS
- DNV
- EPD
Selection Notes
The 3-10 A per-channel threshold, set individually by potentiometer, lets each of the four branch circuits trip before a fault pulls down the shared 24 V bus - choose the DIP-switch load-optimized sequential switch-on mode when downstream loads have high inrush current, such as several PLC power supplies powering up together, rather than the simultaneous mode. The 99% efficiency and 10 W typical power loss keep cabinet heat load low even with all four channels near their 10 A rating. The common signal contact wires a single alarm back to the PLC instead of monitoring four channels individually.
Applications
Selective load distribution downstream of a single 24 V DC power supply, separating PLC, HMI, I/O, and sensor or actuator branch circuits so a short on one branch does not take down the whole 24 V bus.