- Description
The Siemens 6EP3437-8MB00-2CY0 is a SITOP PSU8600 power supply with four independently monitored 24 V DC outputs rated 10 A each (40 A / 960 W total system power), taking 400-500 V 3AC input and offering an integrated PROFINET interface with a built-in web server and OPC UA server for remote diagnostics.
Technical Specifications
| SKU | 6EP3437-8MB00-2CY0 |
| Brand | Siemens |
| Series | SITOP PSU8600 |
| EAN | 4025515154471 |
| Input Type | 3-phase AC |
| Input Voltage AC | 400-500 V (320-575 V operating range) |
| Line Frequency | 50/60 Hz (47-63 Hz) |
| Number of Outputs | 4, individually adjustable 4-28 V |
| Output Voltage | 24 V DC per output |
| Output Current | 10 A per output, 40 A total |
| Output Power | 960 W total (240 W per output) |
| Efficiency | 93% |
| Residual Ripple (max) | 100 mV |
| Communication | Ethernet/PROFINET, OPC UA, 2-port switch (RJ45 x2) |
| Overvoltage Protection | max. 35 V (max. 500 ms) |
| Protection Class | IP20 |
| Ambient Temperature (Operating) | -25 to +60°C |
| Enclosure Dimensions (W x H x D) | 125 x 125 x 150 mm |
| MTBF (at 40°C) | 207,612 h |
| Net Weight | 2.62 kg |
Certifications & Standards
- CE
- cULus
- EAC
- SEMI F47
- BIS
- CB
- Shipbuilding Approval
- ABS
- DNV
- EPD
Selection Notes
The 6EP3437-8MB00-2CY0 is the 4x10 A PROFINET variant of the PSU8600 family, doubling the per-output current of the 4x5 A model for machines with heavier individually-fused 24 V DC branches. As with the smaller model, outputs 1-2 and 3-4 can be paralleled via DIP switch when one branch needs more than 10 A, up to the 960 W system total. The same PROFINET/OPC UA interface reports per-output voltage, current, and DC-OK state, so branch-level diagnostics scale up without adding wiring as the machine's power budget grows. Choose this model over the 4x5 A 8436 variant when connected loads regularly draw more than 5 A per branch; choose the single-output 40 A PSU8600 model instead if the installation does not need four independently supervised circuits.