- Description
The Siemens 6EP3332-0TA00-0AY0 is a SITOP PSU3400 Uni power supply that accepts either a 230 V AC (88-264 V) or an 18-264 V DC input and delivers a stabilized 24 V DC output rated 2.5 A continuous, 3.5 A without derating up to 70 degrees C. Soft-start switch-on avoids output overshoot, and the unit reaches 85% efficiency at 85 W typical supplied power.
Technical Specifications
| SKU | 6EP3332-0TA00-0AY0 |
| Brand | Siemens |
| Series | SITOP PSU3400 |
| Product Designation | Power supply SITOP DC-DC converter |
| Input Type | 1-phase AC or DC, wide range |
| Input Voltage | AC 88 ... 264 V or DC 18 ... 264 V |
| Line Frequency | 50/60 Hz |
| Output Voltage | 24 V DC, adjustable 24-28 V via potentiometer |
| Output Current, rated | 2.5 A (3.5 A up to +70 °C, no derating) |
| Supplied Power, typical | 85 W |
| Efficiency | 85 % |
| Power Loss, typical / no-load | 7 W / 1.5 W |
| Switch-On Behavior | No overshoot of Vout, soft start |
| Overvoltage Protection | Ua < 35 V |
| Short-Circuit Protection | Electronic shutdown, automatic restart |
| Galvanic Isolation | Yes, SELV/ES1 acc. to IEC 62368-1 |
| Protection Class | IP20 |
| Enclosure (W x H x D) | 32 x 100 x 100 mm |
| Mounting | DIN rail EN 60715 35x7.5/15 |
| Ambient Temperature (operation) | -25 ... +70 °C |
| Net Weight | 0.32 kg |
| MTBF at 40 °C | 1,934,648 h |
Certifications & Standards
- CE
- UKCA
- RCM
- CB
Selection Notes
Accepting either 230 V AC or 18-264 V DC on the same terminals, this PSU3400 Uni variant works as a primary AC-fed supply or as a DC-DC converter downstream of a 24 V battery or another DC bus without a different part number. The 3.5 A rating with no derating up to 70 degrees C gives headroom over the 2.5 A typical rated current, and soft-start switch-on avoids inrush transients on sensitive downstream electronics; pick a PSU6200 model instead when only AC input is available and a diagnostic contact is required.
Applications
Suited to panels that may be fed from either AC mains or an existing 24 V DC bus, and to battery-backed or DC-distributed installations needing a compact DC-DC 24 V/2.5 A stage.