- Home
- Power Quality, Metering & Power Supplies
- Siemens 6EP3322-6SB10-0AY0 LOGO!Power 100-240V AC / 15V DC 4A Power Supply Siemens 6EP3322-6SB10-0AY0 LOGO!Power 100-240V AC / 15V DC 4A Power Supply
Siemens 6EP3322-6SB10-0AY0 LOGO!Power 100-240V AC / 15V DC 4A Power Supply
Siemens 6EP3322-6SB10-0AY0 LOGO!Power 100-240V AC / 15V DC 4A Power Supply
Get Quote
- Description
The Siemens 6EP3322-6SB10-0AY0 LOGO!Power supply converts a 100-240 V AC (or 110-300 V DC) wide-range input into a stabilized, adjustable 15 V DC output rated at 4 A. It reaches 88.4% efficiency, provides 40 ms buffering time on power loss, and snaps onto a 35 mm DIN rail in an IP20, Class II enclosure for direct control-cabinet mounting.
Technical Specifications
| SKU (MLFB) | 6EP3322-6SB10-0AY0 |
| Brand | Siemens |
| Series | SITOP LOGO!Power |
| Product Designation | LOGO!Power |
| Input Voltage | 100-240 V AC (85-264 V AC) or 110-300 V DC, 47-63 Hz |
| Input Current | 1.24 A at 120 V, 0.68 A at 230 V |
| Inrush Current | 55 A max at 25 degC |
| Output Voltage | 15 V DC, adjustable 10.5-16.1 V via potentiometer |
| Output Current | 4 A rated (0-4 A range) |
| Output Power | 60 W typ. |
| Efficiency | 88.4% |
| Buffering Time on Power Loss | 40 ms min. at rated output current |
| Short-Circuit Protection | Yes, constant-current characteristic, 5 A typ. |
| Galvanic Isolation | Yes, SELV/ES1 (IEC 62368-1) |
| Protection Class | Class II |
| Degree of Protection | IP20 |
| MTBF at 40 degC | 2,566,680 h |
| Enclosure (W x H x D) | 54 x 90 x 53 mm |
| Operating Temperature | -25...+70 degC, natural convection |
| Net Weight | 0.2 kg |
Certifications & Standards
- CE
- UL 508
- cULus
- EAC
- NEC Class 2
- SEMI F47
- CB
Selection Notes
The output voltage is adjustable from 10.5 to 16.1 V via an onboard potentiometer, so this unit covers applications that need slightly above or below the nominal 15 V rail, not just a fixed 15 V. It supports parallel operation of up to two units to increase available power, which matters if a load exceeds the single-unit 60 W rating. The 40 ms power-loss buffering time is a spec to check against downstream PLC or relay hold-in requirements before assuming ride-through on brief mains dips.
Applications
Sized for LOGO! logic modules and small 15 V DC loads such as relay coils, sensors, or signal circuits in control cabinets, machine builds, and building-automation panels where DIN-rail mounting and a wide 100-240 V AC input range are needed.