- Home
- Power Quality, Metering & Power Supplies
- Siemens 6EP3124-0TA00-0AY0 SITOP PSU3400 24V to 12V 15A DC/DC Converter Siemens 6EP3124-0TA00-0AY0 SITOP PSU3400 24V to 12V 15A DC/DC Converter
Siemens 6EP3124-0TA00-0AY0 SITOP PSU3400 24V to 12V 15A DC/DC Converter
Siemens 6EP3124-0TA00-0AY0 SITOP PSU3400 24V to 12V 15A DC/DC Converter
Get Quote
- Description
The Siemens 6EP3124-0TA00-0AY0 is a SITOP PSU3400 DC/DC converter that steps a 24 V DC input (14-32 V) down to a stabilized 12 V DC output at up to 15 A, with the output adjustable from 12 to 15.5 V via potentiometer. It runs at 91% efficiency, holds a 5 ms minimum buffering time at rated output, and reports output status through a relay contact.
Technical Specifications
| Order Number | 6EP3124-0TA00-0AY0 |
| Brand | Siemens |
| Series | SITOP PSU3400 |
| Product Designation | PSU3400 DC/DC Converter |
| Input Voltage (rated) | 24 V DC |
| Input Voltage Range | 14 ... 32 V DC |
| Input Current (at 24V) | 8.4 A |
| Output Voltage (rated) | 12 V DC |
| Output Voltage Adjustable | 12 ... 15.5 V via potentiometer |
| Output Current (rated) | 15 A |
| Output Power (typical) | 200 W |
| Efficiency | 91% |
| Power Loss (typical) | 21 W |
| Buffering Time (min, at rated output) | 5 ms |
| Signaling | Relay contact (NO, 30 V AC/0.5 A; 30 V DC/1 A) for 12 V OK |
| Protection Class IP | IP20 |
| Operating Resource Protection Class | Class III |
| Galvanic Isolation | Yes, output: SELV, ES1 (IEC 62368-1) |
| Ambient Temperature (Operation) | -25 ... +70 degC |
| Enclosure Dimensions (W x H x D) | 42 x 125 x 120 mm |
| Mounting | DIN rail EN 60715 35x7.5/15 |
| Net Weight | 0.6 kg |
| MTBF at 40 degC | 1,411,273 h |
| Country of Origin | HU |
Certifications & Standards
- CE
- EAC
- RCM
- CB
- Shipbuilding
- ABS
- DNV
Selection Notes
This is the 12 V/15 A tap of the PSU3400 DC/DC family fed from a 24 V DC bus - pick it over the 24 V-output PSU3400 variants when the downstream load genuinely needs 12 V, since the converter does not down-convert further than its fixed output tap. The output adjusts 12-15.5 V via potentiometer, which covers cable-drop compensation on long 12 V runs without a separate boost stage. A 5 ms minimum buffering time at rated output means momentary 24 V bus dips shorter than that do not reach the 12 V load, but longer interruptions need a buffer module or battery stage upstream.
Applications
Converts an existing 24 V DC control bus down to 12 V DC for loads that standardize on 12 V - sensors, relay coils, or auxiliary electronics - without adding a second mains-fed power supply next to the 24 V DC rail already in the cabinet.