- Home
- Power Quality, Metering & Power Supplies
- Siemens 6EP1433-0AA00 SITOP PSU300E 3AC 400-500V 24V/5A DIN Rail Power Supply Siemens 6EP1433-0AA00 SITOP PSU300E 3AC 400-500V 24V/5A DIN Rail Power Supply
Siemens 6EP1433-0AA00 SITOP PSU300E 3AC 400-500V 24V/5A DIN Rail Power Supply
Siemens 6EP1433-0AA00 SITOP PSU300E 3AC 400-500V 24V/5A DIN Rail Power Supply
Get Quote
- Description
The Siemens 6EP1433-0AA00 is a SITOP PSU300E three-phase power supply that converts 400-500 V AC into a stabilized 24 V DC output rated 5 A (120 W). It mounts on a 42 mm-wide DIN rail, holds the output adjustable from 24 to 29 V via potentiometer, and bridges a 50 ms mains dropout at rated load, suited to 24 V loads fed directly from a 400 V three-phase distribution board.
Technical Specifications
| Order Number | 6EP1433-0AA00 |
| Brand | Siemens |
| Series | SITOP PSU300E |
| Product Designation | PSU300E |
| Input Type | 3-phase AC |
| Input Voltage AC | 400...500 V (320...550 V range) |
| Line Frequency | 50/60 Hz (47...63 Hz) |
| Output Voltage | 24 V DC, adjustable 24...29 V via potentiometer (max 120 W) |
| Output Current | 5 A rated (0...5 A range) |
| Output Power | 120 W typical |
| Voltage Tolerance | 3% |
| Residual Ripple | 35 mV typical, 150 mV max |
| Efficiency | 90% |
| Power Loss | 13 W typical at rated load |
| Mains Buffering | 50 ms minimum at 400 V input |
| Inrush Current Limit | 15 A max at 25C |
| Short-Circuit Protection | Electronic shutdown, automatic restart |
| Overvoltage Protection Threshold | less than 60 V |
| Recommended Feeder Protection | 3-pole 6 A MCB characteristic B or C, or MSP 3RV2011-1DA10 |
| Galvanic Isolation | Yes - SELV, ES1 (IEC 62368-1) |
| Protection Class | IP20 / Class I |
| Ambient Temperature (operation) | 0...+60C |
| Enclosure Dimensions (WxHxD) | 42 x 125 x 125 mm |
| Mounting | DIN rail EN 60715 35x7.5/15 |
| Net Weight | 0.6 kg |
| MTBF | 2,389,441 h at 40C |
| Country of Origin | RO |
Certifications & Standards
- CE
- EAC
Selection Notes
The 6EP1433-0AA00 draws directly from a 3-phase 400-500 V distribution board rather than the single-phase 100-230 V input used by the SITOP PSU100 series, which matters where the panel already has three-phase power and a single-phase tap would add wiring. Output is adjustable to 29 V (up to 120 W) via potentiometer, useful for compensating voltage drop on a long 24 V run or lifting the set point for downstream equipment specifying a slightly higher supply. No internal input fuse is fitted, so the recommended external protection, a 6 A characteristic B or C miniature circuit breaker or an equivalent motor-protective circuit breaker, must be installed in the feeder for the unit to be protected against an upstream fault.