- Siemens 6EP1334-3BA10 SITOP PSU200M 120/230-500V AC to 24V DC 10A Power Supply Siemens 6EP1334-3BA10 SITOP PSU200M 120/230-500V AC to 24V DC 10A Power Supply
Siemens 6EP1334-3BA10 SITOP PSU200M 120/230-500V AC to 24V DC 10A Power Supply
Siemens 6EP1334-3BA10 SITOP PSU200M 120/230-500V AC to 24V DC 10A Power Supply
Get Quote
- Description
The Siemens 6EP1334-3BA10 SITOP PSU200M is a DIN-rail power supply converting 120/230-500 V AC input (selector-switch set) to a stabilized 24 V DC output at 10 A, delivering 240 W typical. Efficiency is 91% with a 25 ms buffering time on power loss, adjustable output up to 28.8 V, and a floating alarm relay contact.
Technical Specifications
| SKU | 6EP1334-3BA10 |
| Brand | Siemens |
| Series | SITOP PSU200M |
| Input Type | 1-phase and 2-phase AC, selector switch |
| Input Voltage 1 | 120-230 V (85-264 V range) |
| Input Voltage 2 | 230-500 V (176-550 V range) |
| Input Current | 4.4 A at 120 V, 2.4 A at 230 V, 1.1 A at 500 V |
| Inrush Current Limit (25 C) | 35 A max |
| Output Voltage | 24 V DC, adjustable 24-28.8 V |
| Output Current | 10 A rated (0-10 A) |
| Output Power, typ. | 240 W |
| Efficiency | 91% |
| Residual Ripple, max. | 50 mV |
| Short-Circuit Current, typ. | 12 A (constant current or latching shutdown) |
| Alarm Output | Relay contact, 30 V DC/0.1 A |
| MTBF at 40 C | 1 055 408 h |
| Ambient Temperature, Operation | -25 to +70 C |
| Enclosure Dimensions (W x H x D) | 70 x 125 x 121 mm |
| Mounting | DIN rail EN 60715 35x7.5/15 |
| Net Weight | 0.8 kg |
Certifications & Standards
- CE
- UKCA
- EAC
- RCM
- SEMI F47
- CB
- shipbuilding
- ABS
- DNV
Selection Notes
The PSU200M 10 A variant runs from a 1- or 2-phase AC input set by an onboard selector switch, either 120-230 V single-phase or 230-500 V, so it must be matched to the site voltage before commissioning rather than relying on a fixed wide-range input. At 240 W typical it sizes above the LOGO!Power class of supplies, and the floating alarm relay contact (30 V DC/0.1 A) reporting overload or shutdown status is worth wiring back to the controller on loads where a fault needs a hardwired signal rather than just an LED indication. A buffer module accessory is listed for extending ride-through beyond the 25 ms internal buffering time.
Applications
Sized for cabinet-level 24 V DC distribution feeding multiple S7-1200 or S7-1500 racks, I/O stations, or contactor coils where 240 W of output and a hardwired alarm signal are needed rather than a single small logic controller supply.