- Home
- Power Quality, Metering & Power Supplies
- Schneider Electric METSEPM5350 PowerLogic PM5350 Power Meter Class 0.5S 15th Harmonic 4DI 2DO Power Meter Schneider Electric METSEPM5350 PowerLogic PM5350 Power Meter Class 0.5S 15th Harmonic 4DI 2DO Power Meter
Schneider Electric METSEPM5350 PowerLogic PM5350 Power Meter Class 0.5S 15th Harmonic 4DI 2DO Power Meter
Schneider Electric METSEPM5350 PowerLogic PM5350 Power Meter Class 0.5S 15th Harmonic 4DI 2DO Power Meter
Get Quote
- Description
The Schneider Electric METSEPM5350 is a PowerLogic PM5350 flush-mount power and energy meter with Class 0.5S accuracy to IEC 62053-22. It measures voltage, current, frequency, power factor, active/reactive/apparent power and energy, and resolves harmonics up to the 15th order at 32 samples per cycle. Four digital inputs and two relay outputs are built in for alarming and load control over RS485 Modbus.
Technical Specifications
| Reference | METSEPM5350 |
| Brand | Schneider Electric |
| Range | PowerLogic |
| Device Short Name | PM5350 |
| Accuracy Class | Class 0.5S active energy (IEC 62053-22) |
| Measured Parameters | Voltage, current, frequency, power factor, active/reactive/apparent power, energy, THD to 15th harmonic |
| Sampling Rate | 32 samples/cycle |
| Rated Supply Voltage (Us) | 85-265 V AC 45-65 Hz / 100-300 V DC |
| Rated Current Input (In) | 1 A or 5 A |
| Network Type | 1P+N, 3P, 3P+N |
| Measurement Voltage | 20-277 V AC phase-neutral / 35-480 V AC phase-phase |
| Frequency Range | 45-70 Hz |
| Digital Inputs | 4 |
| Relay Outputs | 2 |
| Communication | RS485, Modbus RTU/ASCII, 9.6/19.2/38.4 kbaud |
| Display | Monochrome graphic LCD, 6 lines |
| Mounting | Flush-mounted, 96 x 96 mm cutout |
| IP Rating | IP30 rear / IP54 display |
| Overvoltage Category | III |
| Operating Temperature | -25 to 70 degC |
| Dimensions (W x D x H) | 96 x 44 x 96 mm |
| Weight | 0.25 kg |
Certifications & Standards
- CE
- cULus
- IEC 61010-1
Selection Notes
The METSEPM5350 accepts a universal 85-265 V AC / 100-300 V DC supply and a selectable 1 A or 5 A CT input, so the same reference covers both direct low-voltage panel feeders and CT-metered branch circuits. Class 0.5S accuracy to IEC 62053-22 meets sub-metering and tenant-billing requirements, and the two relay outputs can drive an alarm or load-shed contact directly from a measured threshold without an external PLC. Choose the PM5560/PM5563 variants when 63rd-harmonic analysis or Ethernet communication is needed; the PM5350 covers RS485-only installations up to the 15th harmonic.