- Home
- Power Quality, Metering & Power Supplies
- Schneider Electric METSEDM6200HCL10RS EasyLogic DM6200H VAF PF Modbus RS485 Power Meter Schneider Electric METSEDM6200HCL10RS EasyLogic DM6200H VAF PF Modbus RS485 Power Meter
Schneider Electric METSEDM6200HCL10RS EasyLogic DM6200H VAF PF Modbus RS485 Power Meter
Schneider Electric METSEDM6200HCL10RS EasyLogic DM6200H VAF PF Modbus RS485 Power Meter
Get Quote
- Description
The Schneider Electric METSEDM6200HCL10RS is an EasyLogic DM6200H digital panel meter that measures voltage, current, frequency, and power factor with Class 1 active energy accuracy to IEC 62053-21. It adds an RS485 port running Modbus to the DM6X00H body, reading locally on a 96 x 96 mm bezel with an 8-segment red LED display and a tricolour load-burden bar.
Technical Specifications
| Reference | METSEDM6200HCL10RS |
| Brand | Schneider Electric |
| Range | EasyLogic |
| Product type | VAF PF digital panel meter |
| Type of measurement | Current, voltage, frequency, RPM |
| Accuracy class | Class 1 |
| Measurement accuracy | Frequency +/- 0.05 %, power factor +/- 0.01, current +/- 1 %, voltage +/- 1 % |
| Rated supply voltage (Us) | 48...277 V AC 45...65 Hz or 48...277 V DC |
| Rated current (In) | 1 A / 5 A |
| Network frequency | 50 Hz / 60 Hz |
| Type of network | 1P+N, 2P, 2P+N, 3P, 3P+N |
| Measurement voltage | 46...277 V AC phase to neutral, 80...480 V AC between phases, up to 999000 V with external VT |
| Sampling rate | 32 samples/cycle |
| Display type | 8-segment red LED, 14.2 mm digit height |
| Communication | Modbus, RS485, screw terminal block |
| Mounting mode | Flush-mounted |
| Dimensions (W x H x D) | 96 x 96 x 62 mm |
| IP degree of protection | IP51 front, IP30 body |
| Ambient operating temperature | -10...60 C |
| Net weight | 300 g |
Certifications & Standards
- CE
- cULus
- IEC 61010-1
- UL 61010-1
Selection Notes
The METSEDM6200HCL10RS is the communicating variant of the DM6X00H panel meter, with an RS485 Modbus port that the no-communication METSEDM6000HCL10NC does not have. Choose it whenever the reading needs to reach a SCADA or BMS point rather than only the local LED display; the measurement range, accuracy class, and mechanical footprint are otherwise identical to the NC version.