- Home
- Power Contactors (AC-3)
- Schneider Electric LC1E25004M7 Easy TeSys Contactor 4P 4NO AC-1 40 A 220 V AC Coil Contactor Schneider Electric LC1E25004M7 Easy TeSys Contactor 4P 4NO AC-1 40 A 220 V AC Coil Contactor
Schneider Electric LC1E25004M7 Easy TeSys Contactor 4P 4NO AC-1 40 A 220 V AC Coil Contactor
Schneider Electric LC1E25004M7 Easy TeSys Contactor 4P 4NO AC-1 40 A 220 V AC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1E25004M7 is a 4-pole Easy TeSys contactor rated 40 A AC-1 for resistive-load switching at up to 440 V. It carries a 220 V AC 50/60 Hz coil with built-in 4NO auxiliary contacts, power and control connections by screw clamp terminals in a 45 mm wide DIN-rail housing.
Technical Specifications
| SKU | LC1E25004M7 |
| Brand | Schneider Electric |
| Range | Easy TeSys |
| Poles | 4P, 4 NO |
| Utilisation Category | AC-1 (resistive load) |
| [Ie] Rated Operational Current | 40 A at ≤440 V AC-1 |
| [Ue] Rated Operational Voltage | ≤690 V AC 50/60 Hz |
| [Uc] Control Circuit Voltage | 220 V AC 50/60 Hz |
| [Ith] Conventional Free Air Thermal Current | 40 A at 55 °C |
| Rated Breaking Capacity | 200 A at 440 V (IEC 60947) |
| [Icw] Rated Short-Time Withstand Current | 240 A, 10 s at 40 °C |
| Associated Fuse Rating | 40 A gG at ≤690 V, coordination type 1 |
| Auxiliary Contact Composition | Without |
| Maximum Operating Rate | 1800 cycles/hour |
| Mechanical Durability | 8 Mcycles mechanical, 0.35 Mcycles electrical |
| Mounting Support | DIN rail or plate |
| IP Degree of Protection | IP2X (IEC 60529) |
| Permissible Ambient Operating Temperature | -5...55 °C |
| Height x Width x Depth | 64 x 56 x 93 mm |
| Net Weight | 0.52 kg |
Certifications & Standards
- CB Scheme
- CE
- CCC
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-4-1
Selection Notes
The LC1E25004M7 is rated AC-1 only, so its 40 A figure applies to resistive loads such as heating elements and must not be read against AC-3 motor contactors of similar current. Four normally-open poles let it switch a complete 3-phase-plus-neutral heating circuit in one device; where motor starting is the application, the 3-pole AC-3 Easy TeSys contactors are the correct choice instead.