The Schneider Electric LC1D38F7 is a TeSys Deca 3-pole (3NO) contactor rated 38 A AC-3 at up to 440 V, switching 18.5 kW motors at 400 V. It provides a 110 V 50/60 Hz AC coil, 1NO+1NC mirror-certified auxiliary contacts and screw clamp terminals for both load and control wiring. Multi-standard certification covers IEC, UL and CSA markets from one reference.
Technical Specifications
| Reference | LC1D38F7 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| GTIN | 3389110352207 |
| Product Type | Contactor |
| Poles | 3P (3NO) |
| Utilisation Category | AC-1, AC-3, AC-3e |
| Rated Operational Voltage (Ue) | ≤ 690 V AC, 25-400 Hz / ≤ 300 V DC |
| Rated Operational Current (Ie), AC-3, ≤440V | 38 A |
| Rated Operational Current (Ie), AC-1, ≤440V | 50 A |
| Motor Power, AC-3 at 400 V | 18.5 kW |
| Control Circuit Voltage (Uc) | 110 V AC, 50/60 Hz |
| Inrush Power | 70 VA |
| Rated Breaking Capacity at 440 V | 550 A, IEC 60947 |
| Rated Short-Time Withstand Current (Icw), 1 s | 430 A at 40 degrees C |
| Rated Insulation Voltage (Ui) | 690 V, IEC 60947-4-1 |
| Auxiliary Contact Composition | 1 NO + 1 NC, mirror contact |
| Terminal Type | Screw clamp (power and control) |
| Maximum Operating Rate | 3600 cyc/h at 60 degrees C |
| Mounting | DIN rail or screw-fixing plate |
| IP Degree of Protection | IP20, front face |
| Dimensions (H x W x D) | 85 x 45 x 92 mm |
| Net Weight | 380 g |
Certifications & Standards
- IEC 60947-4-1
- UL
- CSA
- CCC
- Marine
Selection Notes
The 110 V AC coil on the LC1D38F7 matches the common North American control-transformer secondary, so it drops into existing panel designs without a coil-voltage change. At 38 A AC-3 it switches 18.5 kW motors at 400 V with 550 A breaking capacity at 440 V. Where a 24 V DC or 230 V AC control circuit is used instead, other LC1D38 coil variants share the identical 45 mm frame and mounting pattern.