- Description
The Schneider Electric LC1D12KUE is a 3-pole TeSys Deca Advanced contactor rated 12 A AC-3 at up to 440 V, switching motors up to 5.5 kW at 400 V and 440 V. It uses a sealed, low-consumption 100-250 V AC/DC wide-band electronic coil and includes 1 built-in normally-open and 1 mirror-certified normally-closed auxiliary contact, with screw clamp terminals in a compact 45 mm housing.
Technical Specifications
| Reference | LC1D12KUE |
| Brand | Schneider Electric |
| Range | TeSys Deca Advanced |
| Device Short Name | LC1D |
| Poles | 3P |
| Pole Contact Composition | 3 NO |
| Utilisation Category | AC-1, AC-3, AC-3e |
| [Ie] Rated Current (AC-3, <=440 V) | 12 A |
| [Ie] Rated Current (AC-1, <=440 V) | 25 A |
| Motor Power (400 V AC-3) | 5.5 kW |
| Motor Power (500 V AC-3) | 7.5 kW |
| [Uc] Control Circuit Voltage | 100-250 V AC/DC |
| Coil Technology | Wide-band electronic, low consumption |
| Auxiliary Contact Composition | 1 NO + 1 NC (mirror) |
| [Ue] Rated Operational Voltage | <= 690 V AC |
| Rated Breaking Capacity | 250 A at 440 V |
| Maximum Operating Rate | 3600 cyc/h |
| Mounting Support | Rail, plate |
| IP Degree of Protection | IP20 |
| Ambient Air Temperature (Operation) | -40°C to 60°C |
| Height x Width x Depth | 77 x 45 x 86 mm |
| Net Weight | 0.373 kg |
| GTIN | 3606480987687 |
Certifications & Standards
- CCC
- CSA
- EAC
- UL
- DNV-GL
- EN/IEC 60947-4-1
Selection Notes
The LC1D12KUE's 100-250 V AC/DC coil suits panels standardized on a single wide-band control voltage across both AC and DC supplies, without the 24-60 V band of the BNE coil variant. Up to a 480 V 35 A circuit breaker it reaches 85 kA SCCR, or up to 100 kA with a 600 V 30 A Class J/CC fuse. For the same 12 A rating with a 24-60 V coil instead, use the LC1D12BNE.