The Schneider Electric LC1D115A6KUE is a 3-pole TeSys Deca Advanced contactor rated 115 A AC-3 at up to 440 V, switching motors up to 55 kW at 400 V and 59 kW at 415 V. It uses a 100-250 V AC/DC wide-band electronic coil and connects via lugs-ring terminals or busbars, with 1 built-in normally-open and 1 mirror-certified normally-closed auxiliary contact.
Technical Specifications
| Reference | LC1D115A6KUE |
| Brand | Schneider Electric |
| Range | TeSys Deca Advanced |
| Device Short Name | LC1D |
| Poles | 3P |
| Pole Contact Composition | 3 NO |
| Utilisation Category | AC-3, AC-3e, AC-1, AC-4 |
| [Ie] Rated Current (AC-3, <=440 V) | 115 A |
| [Ie] Rated Current (AC-1, <=440 V) | 200 A |
| Motor Power (400 V AC-3) | 55 kW |
| Motor Power (415 V AC-3) | 59 kW |
| Motor Power (440 V AC-3) | 75 kW |
| [Uc] Control Circuit Voltage | 100-250 V AC/DC |
| Auxiliary Contact Composition | 1 NO + 1 NC (mirror) |
| [Ue] Rated Operational Voltage | <= 1000 V AC |
| Rated Breaking Capacity | 1100 A at 440 V |
| [Icw] Rated Short-Time Withstand Current | 1800 A - 1 s |
| Connections - Terminals | Lugs-ring terminals or busbars |
| Mounting Support | Plate |
| IP Degree of Protection | IP20 |
| Ambient Air Temperature (Operation) | -40°C to 60°C |
| Height x Width x Depth | 152 x 99 x 155 mm |
| Net Weight | 2.2 kg |
| GTIN | 3606487155867 |
Certifications & Standards
- CB Scheme
- cULus
- CE
- UKCA
- EN/IEC 60947-4-1
- EN/IEC 60947-5-1
Selection Notes
The LC1D115A6KUE connects via lugs-ring terminals or busbars rather than cable lugs, suiting panels built around busbar or ring-lug power distribution - an LRD43 overload relay can mount directly below it. Its AC-4 and 1000 V utilisation categories extend beyond pure AC-3 motor starting into heavier-duty switching. For the same 115 A frame with EverLink cable connectors instead of busbars, use the LC1D115AKUE; for a 150 A rating in the EverLink connection style, use the LC1D150AKUE.