The Siemens 6ES7223-1QH32-0XB0 is a SIMATIC S7-1200 digital I/O module (SM 1223) with 8 AC inputs rated 120/230 V AC and 8 relay outputs switching up to 2 A each. It runs from a 24 V DC backplane supply, groups inputs and outputs in sets of 4 for potential separation, and carries IP20, CE, UL/cULus, CSA, FM, and RCM/KC approvals.
Technical Specifications
| SKU | 6ES7223-1QH32-0XB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 |
| Product type designation | SM 1223, DI 8x120/230 V AC, DQ 8x relay |
| Supply voltage, rated (DC) | 24 V (20.4 V to 28.8 V) |
| Number of digital inputs | 8 (groups of 4) |
| Input voltage, rated (AC) | 120/230 V AC |
| Input current, signal 1, typ. | 9 mA |
| Number of digital outputs | 8 (groups of 4) |
| Digital output type | Relay |
| Switching capacity, resistive load, max. | 2 A |
| Output voltage, rated | 5 V DC to 30 V DC / 5 V AC to 250 V AC |
| Number of operating cycles, max. | 10,000,000 mechanical / 100,000 at rated load |
| Output short-circuit protection | No, to be provided externally |
| Potential separation, outputs to backplane bus | 1500 V AC for 1 minute |
| IP degree of protection | IP20 |
| Ambient temperature, horizontal / vertical, max. | 60 degC / 50 degC |
| Dimensions (W x H x D) | 45 mm x 100 mm x 75 mm |
| Weight, approx. | 230 g |
Certifications & Standards
- CE
- CSA
- UL
- cULus
- FM
- RCM
- KC
- Marine
Selection Notes
The 8 AC inputs read 120/230 V AC field devices directly, so this card avoids interposing relays where limit switches or pushbuttons already run on line voltage. On the output side, the 8 relay channels switch either AC (5-250 V AC) or DC (5-30 V DC) loads on the same card, unlike a transistor output module limited to one voltage type, which suits panels mixing AC contactors with DC indicators. Output short-circuit protection is not built in and must be provided externally, which matters when sizing upstream fusing for the relay outputs.
Applications
Machine control panels with mixed 120/230 V AC field inputs and relay-switched AC/DC outputs, such as line-voltage limit switches feeding contactors, solenoids, or pilot lamps from an S7-1200 station.