The Siemens 6ES7155-5BA00-0AB0 is a SIMATIC ET 200MP PROFIBUS interface module (IM 155-5 DP ST) that connects up to 12 S7-1500 I/O modules to a PROFIBUS DP master through a single RS 485 port at up to 12 Mbit/s. It runs from a 24 V DC supply and ships with the PROFIBUS connection plug 6ES7972-0BB70-0XA0 included.
Technical Specifications
| SKU | 6ES7155-5BA00-0AB0 |
| Brand | Siemens |
| Series | SIMATIC ET 200MP |
| Product Type Designation | IM 155-5 DP ST |
| HW Functional Status | from FS01 |
| Firmware Version | V2.0.0 |
| Supply Voltage, rated (DC) | 24 V (19.2 to 28.8 V) |
| Reverse Polarity Protection | Yes |
| Short-Circuit Protection | Yes |
| Mains/Voltage Failure Stored Energy Time | 5 ms |
| Current Consumption, rated | 0.2 A at 24 V DC, without load |
| Current Consumption, max. | 1.2 A at 20.4 V DC and max. load |
| Inrush Current, max. | 4 A |
| Infeed Power to Backplane Bus | 14 W |
| Power Loss, typ. | 4 W |
| Address Space per Module, max. | 64 byte |
| Address Space per Station, max. | 244 byte |
| Modules per Rack, max. | 12 I/O modules |
| Number of PROFIBUS Interfaces | 1; 1 port |
| RS 485 Transmission Rate, max. | 12 Mbit/s |
| PROFIBUS DP Device | Yes |
| PROFIsafe | Yes |
| SYNC / FREEZE Capability | Yes |
| DPV1 | Yes |
| Isolation Tested With | 707 V DC (type test) |
| Ambient Temperature, Horizontal / Vertical, max. | 60 °C / 40 °C |
| Dimensions (W x H x D) | 35 x 147 x 129 mm |
| Weight, approx. | 360 g |
| EAN | 4047623402138 |
Selection Notes
The ST (Standard) designation means this interface module covers standard-speed PROFIBUS DP connectivity for up to 12 S7-1500 modules without the extended IRT diagnostics of a PROFINET HF variant - choose it when the station only needs cyclic DP data exchange and DPV1 acyclic parameterization on a PROFIBUS, not PROFINET, network. PROFIsafe support lets F-modules run in the same rack for fail-safe I/O over the same DP segment. The RS 485 port tops out at 12 Mbit/s, so segment length and repeater count on the DP trunk should be checked against that rate before scaling toward the 12-module limit.
Applications
Head module for a PROFIBUS DP-based ET 200MP station carrying up to 12 S7-1500 I/O modules, including fail-safe PROFIsafe I/O, on plants standardized on PROFIBUS rather than PROFINET.