- Home
- I/O Modules & Remote I/O
- Siemens 6ES7134-7SD51-0AB0 SIMATIC ET 200iSP 4AI RTD PT100/NI100 Ex ib Remote I/O Module Siemens 6ES7134-7SD51-0AB0 SIMATIC ET 200iSP 4AI RTD PT100/NI100 Ex ib Remote I/O Module
Siemens 6ES7134-7SD51-0AB0 SIMATIC ET 200iSP 4AI RTD PT100/NI100 Ex ib Remote I/O Module
Siemens 6ES7134-7SD51-0AB0 SIMATIC ET 200iSP 4AI RTD PT100/NI100 Ex ib Remote I/O Module
Get Quote
- Description
The Siemens 6ES7134-7SD51-0AB0 is a SIMATIC ET200iSP intrinsically safe electronic module with 4 analog inputs for resistance thermometers, PT100 and NI100, plus direct resistance measurement up to 600 ohms. It offers 16-bit resolution, 0.1 percent basic error limit, and ATEX/IECEx Ex ib [ia Ga] IIC T4 Gb certification for Zone 1 gas and Zone 21 dust areas, with IP30 screw/spring-type terminal connections.
Technical Specifications
| SKU (MLFB) | 6ES7134-7SD51-0AB0 |
| Brand | Siemens |
| Series | SIMATIC ET200iSP |
| Product Type Designation | 4AI RTD |
| Number of Analog Inputs | 4 |
| Input Ranges | Pt100, Ni100, resistance 0-600 ohm (also 1,000 ohm) |
| Connection Types | 2-wire, 3-wire, 4-wire resistance measurement |
| Resolution | 16 bit, including overrange and sign |
| Measurement Principle | Integrating (Sigma-Delta) |
| Basic Conversion Time | 80 ms at 50 Hz / 66 ms at 60 Hz |
| Cycle Time (all channels) | 320 ms max |
| Basic Error Limit | +/-0.1% relative to input range |
| Operational Error Limit | +/-0.15% relative to input range |
| Linearity Error | +/-0.015% |
| Current Consumption | 19 mA typ., 22 mA max |
| Power Loss | 0.4 W typ. |
| Ex(i) Ratings | Uo 5.9 V, Io 24 mA, Po 36 mW, Co 43 microF, Lo 50 mH (gas group IIC) |
| ATEX Marking | II 2 G Ex ib [ia Ga] IIC T4 Gb, II 2 D Ex ib [ia IIIC Da] IIC T4 Gb, I M2 Ex ib [ia] I Mb |
| Degree of Protection | IP30 |
| Cable Length | 500 m max, shielded |
| Connection Method | Screw/spring-type terminal |
| Dimensions (W x H x D) | 30 x 129 x 136.5 mm |
| Net Weight | 230 g |
Certifications & Standards
- GL
- ABS
- BV
- DNV
Selection Notes
Supports 2-, 3-, and 4-wire RTD connections on the same channel, so lead-resistance compensation can be matched to the sensor cable run without swapping modules; a 4-wire connection cancels lead resistance entirely for the tightest accuracy, while 2-wire is adequate for short runs. Basic error limit is 0.1% at 25 degC but widens to 0.15% across the full operating temperature range, worth checking against the process tolerance before specifying. The 320 ms max cycle time across all 4 channels is a real-time budget item if the RTD readings feed a fast control loop rather than slow trend monitoring.
Applications
Sized for temperature measurement circuits in ATEX/IECEx Zone 1 gas or Zone 21 dust areas and marine/offshore hazardous locations, such as process vessel or pipeline RTD monitoring on ET200iSP stations, where the sensor wiring itself must remain intrinsically safe.