- Home
- I/O Modules & Remote I/O
- Siemens 6ES7134-7SD00-0AB0 ET200iSP 4AI TC Thermocouple Ex Zone 1 Remote I/O Module Siemens 6ES7134-7SD00-0AB0 ET200iSP 4AI TC Thermocouple Ex Zone 1 Remote I/O Module
Siemens 6ES7134-7SD00-0AB0 ET200iSP 4AI TC Thermocouple Ex Zone 1 Remote I/O Module
Siemens 6ES7134-7SD00-0AB0 ET200iSP 4AI TC Thermocouple Ex Zone 1 Remote I/O Module
Get Quote
- Description
The Siemens 6ES7134-7SD00-0AB0 is an ET200iSP electronic module with 4 analog thermocouple inputs, certified Ex ib [ia Ga] IIC T4 Gb for installation in ATEX and IECEx Zone 1 hazardous areas. It accepts thermocouple types B, C, E, J, K, L, N, R, S, T and U plus a -80 mV to +80 mV voltage range, with 16-bit resolution and internal cold-junction compensation.
Technical Specifications
| SKU | 6ES7134-7SD00-0AB0 |
| Brand | Siemens |
| Series | SIMATIC ET200iSP |
| Product Type Designation | 4AI TC |
| HW Functional Status | 7 |
| Firmware Version | V1.0.1 |
| Number of Analog Inputs | 4 |
| Input Ranges | Voltage -80 to +80 mV; Thermocouple types B, C, E, J, K, L, N, R, S, T, U |
| Resolution, max. | 16 bit (with overrange) |
| Basic Conversion Time | 80 ms at 50 Hz / 66 ms at 60 Hz |
| Temperature Compensation | Internal (via supplied TC sensor module) or external |
| Supply Voltage (DC) | 20.4-28.8 V |
| Current Consumption, typ. | 17 mA |
| Power Loss, typ. | 0.4 W |
| Cable Length, shielded, max. | 50 m |
| Wire-break Diagnosis | Yes, R greater than 1.7 kOhm |
| IP Degree of Protection | IP30 |
| ATEX Marking | II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb, II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb, I M2 Ex ib [ia] I Mb |
| IECEx Certificate | IECEx KEM 05.0008 |
| Connection Method | Screw/spring-type terminal |
| Width x Height x Depth | 30 x 129 x 136.5 mm |
| Net Weight | 0.32 kg |
| Country of Origin | DE |
Certifications & Standards
- GL
- ABS
- BV
- DNV
Selection Notes
The internal cold-junction compensation via the supplied TC sensor module means this 4AI TC card needs no external compensation socket, unlike modules that rely on a separate analog channel for reference temperature. Its Ex ib [ia Ga] IIC T4 Gb rating restricts it to Zone 1 gas and Zone 21 dust areas rather than Zone 0; pick the HART 2-wire variant instead when the field instrument is a 4-20 mA transmitter rather than a bare thermocouple.