- Home
- Communication & Fieldbus Modules
- Siemens 6GK1562-4AA00 SIMATIC NET CP 5624 PCIe x1 Dual-Port PROFIBUS Communication Processor Card Siemens 6GK1562-4AA00 SIMATIC NET CP 5624 PCIe x1 Dual-Port PROFIBUS Communication Processor Card
Siemens 6GK1562-4AA00 SIMATIC NET CP 5624 PCIe x1 Dual-Port PROFIBUS Communication Processor Card
Siemens 6GK1562-4AA00 SIMATIC NET CP 5624 PCIe x1 Dual-Port PROFIBUS Communication Processor Card
Get Quote
- Description
The Siemens 6GK1562-4AA00 CP 5624 is a PCI Express x1 (3.3 V) communications processor with both a DP master and a DP device connection to PROFIBUS on two separate 9-pin Sub-D ports, supplied with a configuration tool and DP-Base software including a DP-RAM interface, PG protocol, and FDL protocol as a single-installation runtime license, class A.
Technical Specifications
| SKU | 6GK1562-4AA00 |
| Brand | Siemens |
| Series | SIMATIC NET |
| Product Type Designation | CP 5624 |
| Transfer Rate, PROFIBUS (both ports) | 9.6 kbit/s ... 12 Mbit/s |
| PROFIBUS Interfaces | 2x 9-pin Sub-D socket (RS 485) |
| Backplane Bus | PCI Express x1, half length |
| Supply Voltage, Backplane | 3.3 V and 12 V |
| Current Consumption | 0.75 A at 3.3 V, 0.3 A at 12 V |
| Power Loss | 6.1 W |
| DP Master, Devices Operable | 124 |
| DP Master I/O Address Range | 30,256 bytes in, 30,256 bytes out |
| DP Device I/O Address Range | 244 bytes in, 244 bytes out |
| DP Services, Master | DPV0, DPV1, DPV2 |
| FMS Connections, max. | 40 |
| S7/PG Connections, max. | 50 |
| Multi-Protocol Connections | 207 per PC station |
| Cards per PC Station | up to 4 |
| Ambient Temperature, Operation | 5 to 60 °C |
| Protection Class | IP00 |
| Dimensions (W x H x D) | 18 x 112 x 168 mm |
| Net Weight | 117 g |
| Country of Origin | DE |
| EAN | 4019169188593 |
Certifications & Standards
- EPD
Selection Notes
The second RS 485 port is the reason to pick this card over the single-port CP 5623: it runs an independent DP master on one port and a DP device connection (244-byte I/O) on the other, from the same PC. Master capacity and DPV0/DPV1/DPV2 support match the CP 5623 exactly, so choose this card specifically when the PC also needs to appear as a slave on a second PROFIBUS network rather than only mastering one.
Applications
PC stations that both master a PROFIBUS DP network and act as a DP device on a separate PROFIBUS segment, such as a gateway or supervisory PC bridging two independent bus systems.