- Home
- Communication & Fieldbus Modules
- Siemens 6GK1562-3AA00 SIMATIC NET CP 5623 PCIe x1 PROFIBUS Communication Processor Card Siemens 6GK1562-3AA00 SIMATIC NET CP 5623 PCIe x1 PROFIBUS Communication Processor Card
Siemens 6GK1562-3AA00 SIMATIC NET CP 5623 PCIe x1 PROFIBUS Communication Processor Card
Siemens 6GK1562-3AA00 SIMATIC NET CP 5623 PCIe x1 PROFIBUS Communication Processor Card
Get Quote
- Description
The Siemens 6GK1562-3AA00 CP 5623 is a PCI Express x1 (3.3 V) communications processor for PROFIBUS, supplied with a configuration tool and DP-Base software including a DP-RAM interface, PG protocol, and FDL protocol as a single-installation runtime license, class A. It operates as a DP master for up to 124 devices with a 30,256-byte input and output address range.
Technical Specifications
| SKU | 6GK1562-3AA00 |
| Brand | Siemens |
| Series | SIMATIC NET |
| Product Type Designation | CP 5623 |
| Transfer Rate, PROFIBUS | 9.6 kbit/s ... 12 Mbit/s |
| PROFIBUS Interface | 9-pin Sub-D socket (RS 485) |
| Backplane Bus | PCI Express x1, half length |
| Supply Voltage, Backplane | 3.3 V and 12 V |
| Current Consumption | 0.72 A at 3.3 V, 0.25 A at 12 V |
| Power Loss | 5.4 W |
| DP Master, Devices Operable | 124 |
| DP Master I/O Address Range | 30,256 bytes in, 30,256 bytes out |
| DP Services, Master | DPV0, DPV1, DPV2 |
| FMS Connections, max. | 40 |
| S7/PG Connections, max. | 50 |
| Multi-Protocol Connections | 207 per PC station |
| Cards per PC Station | up to 4 |
| Ambient Temperature, Operation | 5 to 60 °C |
| Protection Class | IP00 |
| Dimensions (W x H x D) | 18 x 112 x 168 mm |
| Net Weight | 102 g |
| Country of Origin | DE |
| EAN | 4019169188609 |
Certifications & Standards
- EPD
Selection Notes
DP-Base software and the configuration tool ship with the card, so it operates as a standalone DP master without a separate SOFTNET-PB license, unlike the CP 5612/CP 5622. The 124-device DP master capacity and 30,256-byte I/O range are roughly double the CP 5612/CP 5622 figures, matching it to a production master with more slaves than an engineering PG needs. DPV2 support adds isochronous and slave-to-slave data exchange, which DPV0/DPV1-only cards in this family do not offer. Choose the CP 5624 instead when both a master and a device connection are needed on the same PC.
Applications
Standalone PROFIBUS DP master stations running more than 64 slave devices, and applications needing DPV2 isochronous or slave-to-slave communication without additional master software.