- Home
- Communication & Fieldbus Modules
- Siemens 6ES7241-1CA50-0XB0 SIMATIC S7-1200 CB 1241 RS485 Communication Board Siemens 6ES7241-1CA50-0XB0 SIMATIC S7-1200 CB 1241 RS485 Communication Board
Siemens 6ES7241-1CA50-0XB0 SIMATIC S7-1200 CB 1241 RS485 Communication Board
Siemens 6ES7241-1CA50-0XB0 SIMATIC S7-1200 CB 1241 RS485 Communication Board
Get Quote
- Description
The Siemens 6ES7241-1CA50-0XB0 SIMATIC S7-1200 CB 1241 is a communication board that adds one RS 485 interface to a compact CPU, supporting Freeport, ASCII, Modbus RTU master/device, and USS protocols at up to 250 kbit/s. It draws 75 mA from the backplane bus and connects over point-to-point cable runs up to 1000 m.
Technical Specifications
| SKU | 6ES7241-1CA50-0XB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 |
| Product Type Designation | CB 1241 RS 485 |
| Backplane Current, typ. | 75 mA |
| Power Loss, typ. | 0.4 W |
| Interface | 1x RS 485 |
| Transmission Rate, max. | 250 kbit/s |
| Point-to-Point Cable Length, max. | 1 000 m |
| Integrated Protocols | Freeport, ASCII, Modbus RTU master, Modbus RTU device, USS |
| Freeport Telegram Length, max. | 4 kbyte |
| Modbus RTU Master Devices, max. | 247 (32 per segment) |
| IP Degree of Protection | IP20 |
| Ambient Temperature, vertical install | -20 to 50 C |
| Dimensions (W x H x D) | 15 x 62 x 63 mm |
| Weight | 29 g |
Certifications & Standards
- CE
- UL
- cULus
- RCM
- KC
Selection Notes
The CB 1241 plugs into the S7-1200 CPU's onboard communication board slot rather than a rack expansion position, adding RS 485 connectivity without using up a signal-module slot. In Modbus RTU master mode the CPU can poll up to 247 slave devices under standard Modbus addressing, with a maximum of 32 devices per physical segment before a repeater is required; Modbus RTU device mode instead lets another master poll this CPU. The USS protocol, available as a library function, is the relevant mode when the RS 485 link talks to Siemens drives rather than third-party Modbus instruments.
Applications
Adds RS 485 serial connectivity to an S7-1200 for Modbus RTU instrument networks, USS-based drive control loops, or Freeport ASCII communication with third-party serial devices.