- Schneider Electric LZ7H2X4BD TeSys Hybrid Ultra-Compact Starter 3P 0.18-2.4 A 0.75 kW 24 V DC Motor Starter Schneider Electric LZ7H2X4BD TeSys Hybrid Ultra-Compact Starter 3P 0.18-2.4 A 0.75 kW 24 V DC Motor Starter
Schneider Electric LZ7H2X4BD TeSys Hybrid Ultra-Compact Starter 3P 0.18-2.4 A 0.75 kW 24 V DC Motor Starter
Schneider Electric LZ7H2X4BD TeSys Hybrid Ultra-Compact Starter 3P 0.18-2.4 A 0.75 kW 24 V DC Motor Starter
Get Quote
- Description
The Schneider Electric LZ7H2X4BD is a TeSys Hybrid ultra-compact direct-on-line starter with an integrated Safe Torque Off function, combining hybrid power contacts, class 10A thermal overload protection and SIL3/PLe safety in a 22.5 mm wide housing, for 3-phase motors up to 0.75 kW at 400 V. The thermal range is adjustable 0.18-2.4 A on a 24 V DC control circuit.
Technical Specifications
| SKU | LZ7H2X4BD |
| Brand | Schneider Electric |
| Range | TeSys Hybrid |
| Device Short Name | LZ7H |
| Product Type | Ultra-compact starter |
| Motor Starter Type | Direct on line |
| Poles | 3P |
| Rated Operational Voltage (Ue) | 500 V AC |
| Rated Operational Current (Ie, AC-53A, 500 V) | 2.4 A |
| Thermal Protection Adjustment Range | 0.18-2.4 A |
| Motor Power | 0.75 kW at 400 V |
| Control Circuit Voltage (Uc) | 24 V DC |
| Thermal Overload Class | Class 10A (IEC 60947-4-2) |
| Auxiliary Contact | 1 C/O fault signalling |
| Reset | Manual or electrical reset |
| Safety Function | Safe Torque Off (STO), SIL3 (IEC 61508-1), PLe (ISO 13849-1) |
| Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Mounting | DIN rail, by clips |
| Dimensions (W x H x D) | 22.5 x 99 x 114.5 mm |
| Net Weight | 212 g |
| IP Degree of Protection | IP20 |
Certifications & Standards
- IEC 60947-4-2
- UL 60947-4-1
Selection Notes
The built-in STO function lets the LZ7H2X4BD be wired directly into a safety chain without an external safety relay or contactor, at SIL3 per IEC 61508-1 and PLe per ISO 13849-1 — pick it over the non-safety LZ1H2X4BD whenever the application needs a certified safe-stop function. Because the safety function removes automatic reset, only manual or electrical reset is available after a thermal trip, unlike the non-safety variants. Choose the LZ8H2X4BD instead if the motor also needs forward/reverse control.