The Schneider Electric GV4P115S is a TeSys GV4 three-pole motor circuit breaker rated 115 A, providing thermal-magnetic protection for 3-phase motors from 37-55 kW at 400 V with a breaking capacity Icu of 100 kA at 400/415 V. A rotary handle gives local start-stop control, and EverLink BTR screw terminals keep contact resistance stable over repeated torque cycles.
Technical Specifications
| Reference | GV4P115S |
| GTIN | 3606481386861 |
| Brand | Schneider Electric |
| Range | TeSys GV4 |
| Device short name | GV4P |
| Product type | Motor circuit breaker |
| Device application | Motor protection |
| Poles | 3P |
| Trip unit technology | Thermal-magnetic |
| [In] line rated current | 115 A |
| Thermal setting range (Ir) | 65-115 A |
| Tripping class | 10 or 20 (selectable) |
| Magnetic tripping current (Im) | 1955 A (17 x In) |
| Short-time delay (Isd) | 13 x Ir |
| Breaking capacity Icu (400...415 V AC) | 100 kA |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Motor power (400...415 V AC) | 37-55 kW |
| Utilisation category | Category A (IEC 60947-2), AC-3 (IEC 60947-4-1) |
| Control type | Rotary handle |
| Connections - terminals | EverLink BTR screw terminals |
| IP degree of protection | IP40 |
| Ambient air temperature for operation | -25...70 °C |
| Net weight | 1.6 kg |
| Country of origin | PL |
Certifications & Standards
- IEC 60947-2
- IEC 60947-4-1
- UL 60947-4-1
- CSA C22.2 No. 60947-4-1
- CCC
- EAC
- ATEX
- EU-RO MR
Selection Notes
The 115S is the highest breaking-capacity variant in the 115 A frame, rated Icu 100 kA at 400/415 V, so it suits main incomers and high-fault-level switchboards; the 115B and 115N cover the same current and motor power range at lower cost where fault levels are lower.
Applications
Use for direct-on-line motor protection in panels where thermal overload, short-circuit and phase-loss protection must sit in a single rotary-handle device ahead of a GV4P-compatible contactor.