The Schneider Electric RM35HZ21FM is a Harmony RM35-HZ frequency control relay, monitoring a 120-277 V AC supply for over and underfrequency conditions across a 40-70 Hz measurement window. It switches two separate 5 A changeover contacts with an adjustable 0.1-10 second fault delay, in a 35 mm wide DIN rail housing.
Technical Specifications
| Reference | RM35HZ21FM |
| Brand | Schneider Electric |
| GTIN | 3389119405201 |
| Range of Product | Harmony Control Relays |
| Relay Name | RM35HZ21FM |
| Relay Type | Frequency control relay |
| Relay Monitored Parameters | Overfrequency and underfrequency, 50 or 60 Hz |
| [Us] Rated Supply Voltage | 120-277 V AC, non self-powered |
| Measurement Range | 40-70 Hz |
| Threshold Setting | -2 to 10 Hz / -10 to 2 Hz |
| Time Delay Type | Adjustable 0.1-10 s, +/- 10% |
| Output Contacts | 1 C/O + 1 C/O |
| Nominal Output Current | 5 A |
| Switching Capacity | 1250 VA |
| Reset Time | 2000 ms |
| IP Degree of Protection | IP20 terminals, IP30 casing |
| Mounting Support | 35 mm symmetrical DIN rail |
| Width | 1.4 in (35 mm) |
Certifications & Standards
- CE
- GL
- UL
- CSA
- IEC 60255-6
Selection Notes
The two independent 1 C/O outputs on RM35HZ21FM let an over-frequency trip and an under-frequency trip drive separate downstream circuits - useful for generator or wind-turbine protection where over-speed and under-speed events need different responses rather than a single shared alarm contact. Its 120-277 V AC supply range covers both 120 V and 230/277 V control circuits without a separate SKU, and the -2 to 10 Hz and -10 to 2 Hz threshold settings let each output be tuned independently around the 50/60 Hz nominal. Rated for up to 360 operations per hour under full load and immune to supply microbreaks as short as 10 ms, RM35HZ21FM tolerates momentary disturbances without a nuisance trip, a relevant spec where the monitored source is a diesel genset or inverter with a noisier frequency output than utility mains.