- Home
- Molded Case Circuit Breakers (MCCB)
- ABB 1SDA101193R1 XT7H 1600 Ekip Touch Meas.LSI 1600 4p FF 70kA Molded Case Circuit Breaker (MCCB) ABB 1SDA101193R1 XT7H 1600 Ekip Touch Meas.LSI 1600 4p FF 70kA Molded Case Circuit Breaker (MCCB)
ABB 1SDA101193R1 XT7H 1600 Ekip Touch Meas.LSI 1600 4p FF 70kA Molded Case Circuit Breaker (MCCB)
ABB 1SDA101193R1 XT7H 1600 Ekip Touch Meas.LSI 1600 4p FF 70kA Molded Case Circuit Breaker (MCCB)
Get Quote
- Description
ABB's Tmax XT7H 1SDA101193R1 is a four-pole, fixed XT7 moulded case circuit breaker rated 1600 A, with front terminals and a lever operating mechanism. It delivers 70 kA Icu at 415 V AC under performance level H, and the Ekip Touch Meas.LSI release provides long-time, short-time and instantaneous protection plus integrated metering.
Technical Specifications
| SKU | 1SDA101193R1 |
| Brand | ABB |
| Series / Frame | Tmax XT7 (XT7) |
| Catalog Designation | XT7H 1600 Ekip Touch Meas.LSI 1600 4p FF |
| EAN | 8056221014960 |
| Number of Poles | 4P |
| Rated Current (In/Iu) | 1600 A |
| Rated Operational Voltage (Ue) | 690 V AC |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Ultimate Breaking Capacity (Icu) | 100 kA (220-240 V AC) | 70 kA (380-415 V AC) | 65 kA (440 V AC) | 50 kA (500-525 V AC) | 42 kA (690 V AC) |
| Rated Service Breaking Capacity (Ics) | 100 kA (220-240 V AC) | 70 kA (380-415 V AC) | 65 kA (440 V AC) | 50 kA (500-525 V AC) | 42 kA (690 V AC) |
| Rated Short-Time Withstand Current (Icw, 1s) | 20 kA |
| Release / Trip Unit | Ekip Touch Meas.LSI (Electronic - EL) |
| Short-Circuit Performance Level | H |
| Operating Mechanism | Lever (manual) |
| Terminal Connection Type | Front |
| Power Loss per Pole | 94 W |
| Ambient Air Temperature (Operation) | -40 to 125 °C |
| Net Width | 280 mm |
| Net Height | 268 mm |
| Net Depth | 166 mm |
| Net Weight | 12.5 kg |
Certifications & Standards
- IEC/EN 60947-2
Selection Notes
This four-pole 1600 A breaker is the top current step of the XT7 frame with neutral switching, sized for incomers where both the full feeder current and 4-wire disconnection are needed. The Ekip Touch Meas.LSI release gives L/S/I protection with integrated metering, and performance level H carries 70 kA Icu at 415 V AC and 20 kA Icw. Drop to the 3-pole version if the neutral does not need to be switched.