- Description
Four-pole switching meets 800 A continuous current in the ABB 1SDA101134R1, a Tmax XT7S molded case circuit breaker with the Ekip Touch Measuring LSI electronic release. Fixed, front-terminal (FF) construction, a 690 V AC rating, and a 50 kA breaking capacity at 400-440 V AC make it suitable as a four-wire feeder or main breaker.
Technical Specifications
| SKU | 1SDA101134R1 |
| Brand | ABB |
| Series | Tmax XT |
| Extended Product Type | XT7S 800 Ekip Touch Meas.LSI In800 4p FF |
| EAN | 8056221014373 |
| Number of Poles | 4P |
| Rated Current (In/Iu) | 800 A |
| Rated Operational Voltage (Ue) | 690 V AC |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Ultimate Breaking Capacity (Icu) | 85 kA (220-240 V AC) | 50 kA (380-440 V AC) | 45 kA (500-525 V AC) | 30 kA (690 V AC) |
| Rated Service Breaking Capacity (Ics) | 85 kA (220-240 V AC) | 50 kA (380-440 V AC) | 45 kA (500-525 V AC) | 30 kA (690 V AC) |
| Rated Short-time Withstand Current (Icw) | 20 kA |
| Release / Trip Unit | Ekip Touch Measuring LSI |
| Release Type | Electronic (EL) |
| Short-Circuit Performance Level | S |
| Terminal Connection | Front |
| Mounting | Fixed |
| Power Loss per Pole | 24 W |
| Dimensions (W x H x D) | 280 x 268 x 166 mm |
| Net Weight | 12.5 kg |
| Ambient Operating Temperature | -40 to 125 deg C |
Certifications & Standards
- IEC 60947-2
Selection Notes
The four-pole version adds neutral switching to the same 800 A, 50 kA rating as its three-pole sibling - choose it for TN-C-S transitions or where the neutral must be disconnected together with the phases. Like the other non-M units in this frame, the mechanism is lever-only (10,000 mechanical cycles), which is adequate for installations that are not switched often.