- Description
The ABB 1SDA100529R1 is a Tmax XT5H 630 moulded case circuit breaker with an Ekip Dip LS/I electronic release, rated In 630 A across four poles with front terminals. Short-circuit performance class H delivers a 70 kA breaking capacity at 415 V AC, and the LS/I electronic trip unit combines overload (L), short-time delay (S) and instantaneous (I) protection in one adjustable release.
Technical Specifications
| SKU | 1SDA100529R1 |
| Brand | ABB |
| Series | Tmax XT |
| Catalog Designation | XT5H 630 Ekip Dip LS/I In=630 4p F F |
| EAN | 8056221006057 |
| Sub-type | XT5 |
| Number of Poles | 4P |
| Rated Current (In) | 630 A |
| Rated Uninterrupted Current (Iu) | 630 A |
| Release | Ekip Dip LS/I (electronic, type EL) |
| Short-Circuit Performance Level | H |
| Current Type | AC |
| Rated Operational Voltage (Ue) | 690 V AC |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Ultimate Breaking Capacity (Icu) | 100 kA at 220-240 V AC, 70 kA at 380-415 V AC, 65 kA at 440 V AC, 50 kA at 500-525 V AC, 40 kA at 690 V AC |
| Rated Service Breaking Capacity (Ics) | 100 kA at 220-240 V AC, 70 kA at 380-415 V AC, 65 kA at 440 V AC, 50 kA at 500-525 V AC, 30 kA at 690 V AC |
| Rated Short-Time Withstand Current (Icw) | 6 kA |
| Power Loss | 45 W |
| Rated Frequency | 50/60 Hz |
| Dimensions (W x H x D) | 186 x 205 x 103.5 mm |
| Net Weight | 6.4 kg |
Certifications & Standards
- IEC/EN 60947-2
Selection Notes
Stepping up from the 400 A sibling, the 1SDA100529R1 carries the same Ekip Dip LS/I electronic release and H performance class but a higher 6 kA short-time withstand (Icw) to match its larger 630 A frame. At 690 V AC the service breaking capacity (Ics) drops to 30 kA against a 40 kA ultimate rating (Icu), so downstream coordination studies at that voltage should use the lower Ics figure. The electronic LS/I release gives adjustable long-time, short-time and instantaneous settings that the fixed TMA version of this frame does not offer.