- ABB 1SDA080854R1 XT1H 160 TMD 40-450 4p F F 70kA Molded Case Circuit Breaker (MCCB) ABB 1SDA080854R1 XT1H 160 TMD 40-450 4p F F 70kA Molded Case Circuit Breaker (MCCB)
ABB 1SDA080854R1 XT1H 160 TMD 40-450 4p F F 70kA Molded Case Circuit Breaker (MCCB)
ABB 1SDA080854R1 XT1H 160 TMD 40-450 4p F F 70kA Molded Case Circuit Breaker (MCCB)
Get Quote
- Description
The XT1H 160 TMD 40-450 4p F F, ABB 1SDA080854R1, is a fixed four-pole Tmax XT1 moulded case circuit breaker with a 160 A frame, thermomagnetic TMD release set 28-40 A, and fixed magnetic trip at 450 A. It matches the 70 kA Icu at 415 V AC and front-terminal construction of the lower-setting XT1H 160 breaker, differing only in its higher overload range.
Technical Specifications
| SKU | 1SDA080854R1 |
| Brand | ABB |
| Series | Tmax XT |
| Catalog Designation | XT1H 160 TMD 40-450 4p F F |
| Sub-type | XT1 |
| EAN | 8015644873820 |
| Number of Poles | 4P |
| Rated Current (In) | 160 A |
| Rated Uninterrupted Current (Iu) | 160 A |
| Rated Operational Voltage (Ue/Ur) | 690 V |
| Rated Insulation Voltage (Ui) | 800 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Release | TMD, thermomagnetic (TM) |
| Setting Range | 28...40 A |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 450 A |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 100 kA (220-240 V AC) / 70 kA (380-415 V AC) / 65 kA (440 V AC) / 50 kA (500 V AC) / 35 kA (525 V AC) / 10 kA (690 V AC) / 70 kA (250 V DC, 2 poles in series) / 70 kA (500 V DC, 3 poles in series) |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 80 kA (220-240 V AC) / 52.5 kA (380 V AC) / 37.5 kA (415 V AC) / 32.5 kA (440 V AC) / 25 kA (500 V AC) / 17.5 kA (525 V AC) / 5 kA (690 V AC) / 52.5 kA (250 V DC, 2 poles in series) / 52.5 kA (500 V DC, 3 poles in series) |
| Short-Circuit Performance Level | H |
| Current Type | AC/DC |
| Power Loss | 7.8 W |
| Terminal | Front |
| Opening Time | 30 ms (with SOR) / 30 ms (with UVR) |
| Net Weight | 1.3 kg |
Certifications & Standards
- IEC 60947-2
Selection Notes
The 28-40 A overload setting on this TMD release sits higher in the XT1H 160 frame's adjustment range than the 22.4-32 A version, so pick it for loads closer to the frame's rated current rather than lightly loaded feeders. The fixed 450 A instantaneous trip and 70 kA Icu (415 V AC) H-class rating are unchanged, so the overload setting is the main factor driving the choice between the two.