- Home
- Miniature Circuit Breaker
- ABB 2CDS251001R0325 S201-B32 1P 32A 6kA B-Curve DIN-Rail Miniature Circuit Breaker ABB 2CDS251001R0325 S201-B32 1P 32A 6kA B-Curve DIN-Rail Miniature Circuit Breaker
ABB 2CDS251001R0325 S201-B32 1P 32A 6kA B-Curve DIN-Rail Miniature Circuit Breaker
$5.69
- Description
The ABB S201-B32 miniature circuit breaker (SKU: 2CDS251001R0325) is a 1-pole, 32 A, B-curve MCB from the S200 series, rated at 230/400 V AC with a breaking capacity of 6 kA per IEC/EN 60898-1. Designed for DIN-rail mounting in residential, commercial, and light industrial distribution boards, the S201-B32 provides reliable overcurrent and short-circuit protection with a compact 17.5 mm wide profile.
Technical Specifications
| Catalog Number | S201-B32 |
| SKU | 2CDS251001R0325 |
| Brand | ABB |
| Series | S200 |
| Model | S201 |
| EAN / Barcode | 4016779465304 |
| Number of Poles | 1P |
| Rated Current | 32 A |
| Trip Curve | B |
| Rated Voltage | 230/400 V AC |
| Breaking Capacity (Icu) | 6 kA |
| Mounting Type | DIN-Rail |
| Dimensions (W × H × D) | 17.5 mm × 88 mm × 69 mm |
| Weight | 0.12 kg |
| Product Type | Miniature Circuit Breaker (MCB) |
Certifications & Standards
- IEC/EN 60898-1: International and European standard for household and similar installations MCBs
- IEC/EN 60947-2: International and European standard for low-voltage switchgear circuit breakers
- IEC 60898-1: IEC standard for overcurrent protection of household and similar installations
- EN 60898-1: European harmonised standard for miniature circuit breakers
- EN 60947-2: European standard for low-voltage switchgear and controlgear circuit breakers
- IEC 60898-1230: Supplementary IEC standard designation for MCB applications
- IEC 60068-2: Environmental testing standard for durability and reliability
- EN45555: General methods for assessing the ability of energy-related products to be repaired and recycled
- EN 60664: Insulation coordination for equipment within low-voltage systems
- UL 1077: UL standard for supplementary protectors for use in electrical equipment (North America)
- CSA: Canadian Standards Association approval for use in North American markets
- CE: Conformité Européenne — complies with applicable EU directives
- UKCA: UK Conformity Assessed — complies with applicable UK regulations post-Brexit
- RoHS: Restriction of Hazardous Substances — free from restricted hazardous materials
- REACH: Compliance with EU chemical safety regulation
- WEEE: Waste Electrical and Electronic Equipment directive compliance
Applications & Use Cases
- Overcurrent and short-circuit protection in residential distribution boards
- Commercial building final circuit protection up to 32 A
- Light industrial control panels and machine wiring
- Protection of resistive and slightly inductive loads (B-curve: trips at 3–5× In)
- DIN-rail mounted consumer unit and sub-board installations
- Feeder circuit protection in automation and control cabinets
Frequently Asked Questions
What does the "B" curve mean on the S201-B32?
The B trip curve means the breaker trips instantaneously at 3–5 times the rated current (3–5× 32 A = 96–160 A). This is ideal for resistive loads such as lighting circuits, heating elements, and cable protection where low inrush currents are expected.
Is the ABB S201-B32 compatible with ABB auxiliary contacts and residual current blocks?
Yes. The S200 series is designed to accept a wide range of ABB accessories including auxiliary contacts, shunt trips, undervoltage releases, and residual current blocks (RC2xx series), enabling flexible system configurations.
Can the S201-B32 be used in a 400 V three-phase system?
As a 1-pole breaker, the S201-B32 protects a single phase conductor. It is rated at 230/400 V AC, making it suitable for use within a 400 V TN or TT three-phase system to protect individual phase conductors.