The Schneider Electric LV481444 FuPacT GSD400 is a 4-pole switch disconnector fuse rated 400 A at up to 690 V AC, built for front or right-side handle control. It takes DIN NH2 fuses and protects distribution circuits in buildings, infrastructure and industrial plants against short-circuits and overloads, with a 50 kA breaking capacity with fuses at 415 V and 690 V.
Technical Specifications
| SKU | LV481444 |
| Brand | Schneider Electric |
| Range | FuPacT |
| Product | FuPacT GS |
| Product type | Switch-disconnector-fuse |
| Poles | 4P |
| Number of fuse carriers | 4 |
| Fuse type / size | DIN NH2 |
| [Ue] Rated operational voltage | 690 V AC 50/60 Hz (800 V AC AC-20) |
| [Ui] Rated insulation voltage | 800 V AC |
| [Uimp] Rated impulse withstand voltage | 8 kV |
| [Ie] Rated operational current | 400 A at 220/240-660/690 V AC, AC-22A/AC-22B |
| [Iq] Breaking capacity with fuses | 50 kA at 415 V and 690 V AC |
| Rated operational power | 220 kW at 380/400 V; 295 kW at 660/690 V |
| Type of operating handle | Direct frontal, external frontal, external right side |
| Mounting | Vertical, fixed, on backplate |
| Connections | Power circuit: bare cable connectors 45 mm²; lugs-ring terminals 185-240 mm² |
| Tightening torque | 25 N.m |
| Dimensions (W x H x D) | 318 x 205 x 149 mm |
| Net weight | 6.1 kg |
| IP degree of protection | IP20 (with terminal cover) |
| Ambient temperature (operation) | -20...70 °C |
Certifications & Standards
- CE
- CCC
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-3
Selection Notes
The GSD400 4P adds a fourth switched pole and internal neutral links to the 3-pole GSD400, for circuits needing a switched rather than solid neutral; it shares the 3-pole version's 400 A rating, NH2 fuse size and 50 kA breaking capacity, in a 318 mm wide housing. Choose the 3-pole variant where the neutral does not need to be switched. Only AC-22A/AC-22B utilisation categories are rated at this frame, so confirm the duty is switching rather than frequent AC-23 motor-type operation.