- Home
- Fuse Switch Disconnectors
- Schneider Electric LV480851 Fupact ISFL160 3P 160 A NH00/NH000 Fuse Switch Disconnector Schneider Electric LV480851 Fupact ISFL160 3P 160 A NH00/NH000 Fuse Switch Disconnector
Schneider Electric LV480851 Fupact ISFL160 3P 160 A NH00/NH000 Fuse Switch Disconnector
Schneider Electric LV480851 Fupact ISFL160 3P 160 A NH00/NH000 Fuse Switch Disconnector
Get Quote
- Description
The Schneider Electric LV480851 is a three-pole Fupact ISFL160 fuse-switch disconnector rated 160 A at 690 V AC for AC-21B duty, sized for NH00/NH000 fuse links and built for 60 mm busbar, cable connectors mounting with cable connectors, 95 mm². It carries a 100 kA at 415–690 V AC breaking capacity with fuses and a 5 kA for 1 s short-time withstand rating.
Technical Specifications
| Reference | LV480851 |
| Brand | Schneider Electric |
| Range | FuPacT |
| Device short name | ISFL160 |
| Poles | 3P, switchable as one 3-pole unit |
| Fuse type / size | DIN NH00/NH000 |
| [Ith] conventional thermal current | 160 A at 40 °C (12 W per fuse) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz (800 V AC AC-20); 800 V DC DC-20 |
| [Ui] / [Uimp] insulation / impulse withstand voltage | 1000 V AC / 1000 V DC / 8 kV |
| [Ie] rated operational current | 160 A, AC-21B/AC-22B, 220–690 V AC (80 A at 800 V AC); 160 A, AC-23B, 220–415 V AC |
| Breaking capacity with fuses | 100 kA at 415–690 V AC |
| [Icw] rated short-time withstand current | 5 kA for 1 s |
| Rated making/breaking capacity | 7.65 kA at 690 V (rated making/breaking) |
| Control type | Fuse carriers handle |
| Mounting | Busbars, 60 mm, hook terminal |
| Connections / tightening torque | Cable connectors, 95 mm² (14 N.m) |
| Dimensions (W x H x D) / net weight | 50 mm x 405 mm x 123 mm / 1.3 kg |
| IP degree of protection | IP20 (IEC 60529) |
| Standard | IEC 60947-1, IEC 60947-3 |
Certifications & Standards
- EN/IEC 60947-1
- EN/IEC 60947-3
Selection Notes
The LV480851 switches all three poles together from a single handle, rated 160 A with a 100 kA at 415–690 V AC breaking capacity with fuses installed. Choose the 60 mm busbar, cable connectors variant over the other ISFL160 mounting options when the busbar spacing and cable size in the panel match this connection type.