- Home
- Fuse Switch Disconnectors
- Schneider Electric LV480806 Fupact ISFT400 3P 400 A NH2 Fuse Switch Disconnector Schneider Electric LV480806 Fupact ISFT400 3P 400 A NH2 Fuse Switch Disconnector
Schneider Electric LV480806 Fupact ISFT400 3P 400 A NH2 Fuse Switch Disconnector
Schneider Electric LV480806 Fupact ISFT400 3P 400 A NH2 Fuse Switch Disconnector
Get Quote
- Description
The Schneider Electric LV480806 is a three-pole Fupact ISFT400 fuse-switch disconnector rated 400 A at 690 V AC for AC-21B duty, sized for NH2 fuse links and built for backplate mounting with m10 terminals. It carries a 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC breaking capacity with fuses and a 15.2 kA for 1 s short-time withstand rating.
Technical Specifications
| Reference | LV480806 |
| Brand | Schneider Electric |
| Range | FuPacT |
| Device short name | ISFT400 |
| Poles | 3P (3 fuse carriers) |
| Fuse type / size | DIN NH2 |
| [Ith] conventional thermal current | 400 A at 40 °C (34 W per fuse) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz (800 V AC AC-20); 440 V DC (800 V DC DC-20) |
| [Ui] / [Uimp] insulation / impulse withstand voltage | 1000 V AC / 1000 V DC / 8 kV |
| [Ie] rated operational current | 400 A, AC-21B, 220–690 V AC; 400 A, AC-22B, up to 690 V AC; 400 A DC-21B/DC-22B at 220–440 V DC (3 poles in series) |
| Breaking capacity with fuses | 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC |
| [Icw] rated short-time withstand current | 15.2 kA for 1 s |
| Rated making/breaking capacity | 30.4 kA at 690 V |
| Control type | Fuse carriers handle |
| Mounting | Backplate |
| Connections / tightening torque | M10 terminals (20 N.m) |
| Dimensions (W x H x D) / net weight | 210 mm x 306 mm x 130 mm / 2 kg |
| IP degree of protection | IP3x front face (IEC 60529) |
| Standard | IEC 60947-1, IEC 60947-3 |
Certifications & Standards
- CE
- CCC
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-3
Selection Notes
The LV480806 is a fixed, non-switchable ISFT400 disconnector rated 400 A, sized for NH2 fuse links and a 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC breaking capacity with fuses installed. Pick the backplate version over the other ISFT400 mounting variants in this range when it matches the busbar or cable connection already used in the panel.