- Home
- Fuse Switch Disconnectors
- Schneider Electric LV480801 Fupact ISFT160 3P 160 A NH00 Fuse Switch Disconnector Schneider Electric LV480801 Fupact ISFT160 3P 160 A NH00 Fuse Switch Disconnector
Schneider Electric LV480801 Fupact ISFT160 3P 160 A NH00 Fuse Switch Disconnector
Schneider Electric LV480801 Fupact ISFT160 3P 160 A NH00 Fuse Switch Disconnector
Get Quote
- Description
The Schneider Electric LV480801 is a three-pole Fupact ISFT160 fuse-switch disconnector rated 160 A at 690 V AC for AC-21B duty, sized for NH00 fuse links and built for backplate mounting with m8 terminals. It carries a 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC breaking capacity with fuses and a 5 kA for 1 s short-time withstand rating.
Technical Specifications
| Reference | LV480801 |
| Brand | Schneider Electric |
| Range | FuPacT |
| Device short name | ISFT160 |
| Poles | 3P (3 fuse carriers) |
| Fuse type / size | DIN NH00 |
| [Ith] conventional thermal current | 160 A at 40 °C (12 W per fuse) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz (800 V AC AC-20); 440 V DC (800 V DC DC-20) |
| [Ui] / [Uimp] insulation / impulse withstand voltage | 1000 V AC / 1000 V DC / 8 kV |
| [Ie] rated operational current | 160 A, AC-21B and AC-22B, 220–690 V AC; 160 A DC-21B at 220 V DC, 125 A DC-21B at 440 V DC (3 poles in series) |
| Breaking capacity with fuses | 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC |
| [Icw] rated short-time withstand current | 5 kA for 1 s |
| Rated making/breaking capacity | 7.65 kA at 690 V |
| Control type | Fuse carriers handle |
| Mounting | Backplate |
| Connections / tightening torque | M8 terminals (5 N.m) |
| Dimensions (W x H x D) / net weight | 106 mm x 206 mm x 80 mm / 0.6 kg |
| IP degree of protection | IP3x front face (IEC 60529) |
| Standard | IEC 60947-1, IEC 60947-3 |
Certifications & Standards
- CE
- CCC
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-3
Selection Notes
The LV480801 is a fixed, non-switchable ISFT160 disconnector rated 160 A, sized for NH00 fuse links and a 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC breaking capacity with fuses installed. Pick the backplate version over the other ISFT160 mounting variants in this range when it matches the busbar or cable connection already used in the panel.