- Home
- DIN Rail Power Supplies (24V DC)
- Siemens 6EP3336-8MB00-2CY0 SITOP PSU8600 24V/20A 4x5A PN Power Supply Siemens 6EP3336-8MB00-2CY0 SITOP PSU8600 24V/20A 4x5A PN Power Supply
Siemens 6EP3336-8MB00-2CY0 SITOP PSU8600 24V/20A 4x5A PN Power Supply
Siemens 6EP3336-8MB00-2CY0 SITOP PSU8600 24V/20A 4x5A PN Power Supply
Get Quote
- Description
The Siemens 6EP3336-8MB00-2CY0 is a SITOP PSU8600 power supply that converts a 100-240 V AC input into four independently adjustable 24 V DC outputs, 5 A each for 20 A total, over a PROFINET interface with an integrated OPC UA server. Each output is individually current-limit adjustable from 0.5 to 5 A, and the unit reaches 92% efficiency at 480 W typical supplied power.
Technical Specifications
| SKU | 6EP3336-8MB00-2CY0 |
| Brand | Siemens |
| Series | SITOP PSU8600 |
| Product Designation | Power supply SITOP PSU8600 |
| Input Type | 1-phase or 2-phase AC or DC, wide range |
| Input Voltage | AC 100 ... 240 V / DC 110 ... 220 V |
| Line Frequency | 50/60 Hz |
| Number of Outputs | 4, individually adjustable 4-28 V |
| Output Current, per output rated | 5 A (20 A total system) |
| Output Power, per output max. | 120 W (480 W overall system) |
| Communication Interface | PROFINET / Ethernet, integrated OPC UA server, 2-port switch |
| Supplied Power, typical | 480 W |
| Efficiency | 92 % |
| Power Loss, typical / no-load | 39 W / 14 W |
| Current-Limit Adjustment, per output | 0.5 ... 5 A via potentiometer or IE/PN interface |
| Overvoltage Protection | max. 35 V (max. 500 ms) |
| Short-Circuit Protection | Electronic overload cut-off; Output 4 configurable for constant current |
| Galvanic Isolation | Yes, SELV/ES1 acc. to IEC 62368-1 |
| Protection Class | IP20 |
| Enclosure | Plug-in terminals with screwed connection |
| Mounting | DIN rail mount, PROFINET 2-port switch |
| Ambient Temperature (operation) | -25 ... +60 °C |
| Net Weight | 2.2 kg |
Certifications & Standards
- CE
- EAC
- SEMI F47
- CB
- Shipbuilding
- ABS
- EPD
Selection Notes
Four independently configurable 24 V/5 A outputs on one PROFINET-connected unit let this PSU8600 replace up to four separate DIN-rail supplies while exposing per-output voltage, current limit and diagnostics over the integrated OPC UA server. DIP-switch parallel pairing (Output 1 with 2, or 3 with 4) doubles current on a pair of channels when one machine zone needs more than 5 A, and configurable sequential switch-on (25 ms, 100 ms, or load-optimized) staggers inrush across the four rails on power-up; choose a single-output PSU6200 instead when the application does not need PROFINET-based per-channel monitoring.
Applications
Fits machine builders standardizing on PROFINET-monitored 24 V distribution, where four separately diagnosable output channels replace individual point-of-load supplies and feed status back to the PLC or a SCADA layer via OPC UA.