Get Quote
- Description
The Siemens 6EP4143-8JB00-0XY0 is a SITOP BAT8600 LiFePO4 battery module that stores 358 W-h at 48 V DC for the SITOP UPS8600 uninterruptible power system, delivering 20 A rated output current. Its maintenance-free lithium iron phosphate cells bridge roughly 21 minutes at a 960 W system load, and up to five modules can be paralleled to extend backup time.
Technical Specifications
| SKU | 6EP4143-8JB00-0XY0 |
| Brand | Siemens |
| Series | SITOP BAT8600 |
| EAN | 4025515155096 |
| Product Designation | Battery module 358 Wh |
| Battery Type | Maintenance-free LiFePO4 rechargeable battery |
| Energy Content | 358 W-h |
| Output Voltage | 48 V DC |
| Output Current, Rated | 20 A |
| Bridging Time at 960 W Load | typ. 21 min |
| Bridging Time at 480 W Load | typ. 42 min |
| Max Parallel Modules | 5 |
| Short-Circuit Protection | Blade-type fuse 40 A, 58 V DC |
| Overload Protection | Valve control |
| Display | 3-color LED for module operating state |
| Protection Class IP | IP20 |
| Operating Resource Protection Class | Class III |
| UL/cULus Approval | cULus (UL 61010-1 3rd Ed., UL 61010-2-201 2nd Ed.) |
| Ambient Temperature, Operation | -10 ... +50 C |
| Service Life at 10 C | typ. 15 a |
| Service Life at 20 C | typ. 13 a |
| Service Life at 30 C | typ. 8 a |
| Service Life at 40 C | typ. 4 a |
| Service Life at 50 C | typ. 2 a |
| Number of Batteries | 4 |
| Enclosure W x H x D | 322 x 187 x 110 mm |
| Mounting | Wall mounting, keyhole for M4 screws |
| Net Weight | 7.1 kg |
Certifications & Standards
- CE
- EAC
- CB
- Shipbuilding
- ABS
- DNV
- EPD
Selection Notes
Service life falls sharply with ambient temperature: 15 years at 10 C drops to 2 years at 50 C, so cabinet ventilation and mounting location drive the replacement interval more than the headline capacity rating does. At a 960 W system load the module bridges about 21 minutes; halving the load to 480 W nearly doubles that to 42 minutes, which matters when sizing a controlled-shutdown window against the actual downstream draw. Up to five BAT8600 modules can be paralleled on the same UPS8600 bus to extend runtime without changing the charger or communication wiring.