- Home
- DC UPS & Buffer Modules
- Siemens 6EP4136-3AB00-0AY0 SITOP UPS1600 24V DC 20A Uninterruptible Supply Siemens 6EP4136-3AB00-0AY0 SITOP UPS1600 24V DC 20A Uninterruptible Supply
Siemens 6EP4136-3AB00-0AY0 SITOP UPS1600 24V DC 20A Uninterruptible Supply
Siemens 6EP4136-3AB00-0AY0 SITOP UPS1600 24V DC 20A Uninterruptible Supply
Get Quote
- Description
The Siemens 6EP4136-3AB00-0AY0 is a SITOP UPS1600 DC uninterruptible power supply module rated 24 V DC at 20 A, providing 21-29 V input buffering with an adjustable cut-in threshold and a rotary-switch-selectable backup time from 0.5 to 20 minutes. It delivers up to 60 A peak, runs at 97.7% efficiency with 10 W typical power loss, and carries an IP20 rating in a compact 50 x 139 x 125 mm DIN-rail enclosure weighing 0.39 kg.
Technical Specifications
| SKU | 6EP4136-3AB00-0AY0 |
| Brand | Siemens |
| Series | SITOP UPS1600 |
| Input Voltage | 21-29 V DC (24 V DC rated) |
| Output Voltage, Normal / Buffering | 24 V DC / 18.5-27 V DC |
| Output Current, Rated | 20 A, 0-60 A range |
| Peak Current | 60 A |
| Charging Current | 0.1-4 A |
| Cut-in Threshold, Adjustable | 21-25 V DC, 7 steps |
| Backup Time, Adjustable | 0.5/1/2/5/10/20 min or max. |
| Efficiency | 97.7% |
| Power Loss, typ. | 10 W |
| Supplied Power, typ. | 480 W |
| Protection Class | IP20 |
| Dimensions (W x H x D) | 50 x 139 x 125 mm |
| Net Weight | 0.39 kg |
| MTBF at 40 C | 408,654 h |
Certifications & Standards
- CE
- UKCA
- EAC
- CB
- ABS
- DNV
- EPD
Selection Notes
The rotary-coded backup-time switch (0.5 to 20 minutes, or maximum) sets how long the 24 V rail rides through a supply interruption before the connected battery module is exhausted, letting the same UPS1600 serve either a quick-ride-through role or a full shutdown-sequence role without reprogramming. The adjustable cut-in threshold (21-25 V in seven steps) lets it buffer only on a genuine dip rather than normal ripple from a lightly loaded 24 V supply. At 20 A rated and 60 A peak, it covers inrush from contactors and solenoids during the switchover without derating the connected battery module.
Applications
Used to bridge short mains interruptions for PLCs, I/O, and drives on a 24 V DC bus in control cabinets where an orderly shutdown or ride-through is required instead of an immediate loss of power.