- Home
- DC UPS & Buffer Modules
- Siemens 6EP1933-2EC41 SITOP UPS500S 24V DC/15A 2.5kWs DC UPS Module Siemens 6EP1933-2EC41 SITOP UPS500S 24V DC/15A 2.5kWs DC UPS Module
Siemens 6EP1933-2EC41 SITOP UPS500S 24V DC/15A 2.5kWs DC UPS Module
Siemens 6EP1933-2EC41 SITOP UPS500S 24V DC/15A 2.5kWs DC UPS Module
Get Quote
- Description
The Siemens 6EP1933-2EC41 SITOP UPS500S is a maintenance-free DC uninterruptible power supply module that bridges 24 V DC power interruptions using an internal capacitor energy store. Rated for 24 V DC input and 15 A output, it holds a 2.5 kWs energy reserve — enough to sustain full load for 3 seconds or a reduced load for up to 38 seconds — and reports status through a USB interface and floating relay contacts.
Technical Specifications
| SKU | 6EP1933-2EC41 |
| Brand | Siemens |
| Series | SITOP UPS500S |
| EAN | 4025515152392 |
| Input Voltage | 24 V DC |
| Input Voltage Range | 22 ... 29 V |
| Rated Input Current | 15.2 A |
| Output Voltage | 24 V DC ± 3 % |
| Rated Output Current | 15 A |
| Output Current Range | 0 ... 15 A |
| Peak Current | 25 A |
| Energy Content | 2.5 kWs |
| Bridging Time | 15 A for 3 s / 10 A for 6 s / 5 A for 15 s / 2 A for 38 s |
| Efficiency | 97.5 % |
| Power Loss | 9 W |
| Interface | USB |
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | 0 ... 60 °C |
| Dimensions (W x H x D) | 120 x 125 x 125 mm |
| Net Weight | 1 kg |
Certifications & Standards
- CE
- EAC
- Shipbuilding
- ABS
- DNV
- EPD
Selection Notes
The 15 A bridging rating covers three distinct scenarios rather than a single number: full 15 A load for 3 s, a reduced 10 A draw for 6 s, or 5 A for 15 s — the actual ride-through time depends on how much of the 15 A output the connected load draws. Applications needing longer coverage than the onboard 2.5 kWs capacitor bank provides can add an extension module instead of stepping up to a larger UPS. The USB interface plus floating OK/ALARM/BAT>85% contacts let the module report buffering state to a PLC without extra I/O wiring beyond the existing 24 V DC distribution.
Applications