- Home
- Contactor Relays & Auxiliary Contactors
- Schneider Electric CAD50M7 TeSys Deca Control Relay 5 NO 220 V AC Coil Screw Clamp Auxiliary Contactor Schneider Electric CAD50M7 TeSys Deca Control Relay 5 NO 220 V AC Coil Screw Clamp Auxiliary Contactor
Schneider Electric CAD50M7 TeSys Deca Control Relay 5 NO 220 V AC Coil Screw Clamp Auxiliary Contactor
Schneider Electric CAD50M7 TeSys Deca Control Relay 5 NO 220 V AC Coil Screw Clamp Auxiliary Contactor
Get Quote
- Description
The Schneider Electric CAD50M7 is a TeSys Deca control relay with a 5 NO contact composition, rated 10 A Ith at up to 690 V AC, and a 220 V AC 50/60 Hz control circuit. It switches electromagnetic loads in AC-15 and DC-13 duty and wires into the control circuit of a motor starter or automation panel through screw clamp terminals.
Technical Specifications
| Reference | CAD50M7 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| Product Type | Control relay |
| GTIN | 3389110842463 |
| Pole Contact Composition | 5 NO |
| Utilisation Category | AC-15, AC-14, DC-13 |
| [Ue] Rated Operational Voltage | ≤ 690 V AC, 25...400 Hz |
| [Uc] Control Circuit Voltage | 220 V AC 50/60 Hz |
| [Ith] Conventional Free Air Thermal Current | 10 A |
| Rated Making Capacity (Irms) | 140 A AC / 250 A DC |
| [Icw] Rated Short-Time Withstand Current | 100 A (1 s) / 120 A (500 ms) / 140 A (100 ms) |
| [Ui] Rated Insulation Voltage | 690 V |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV |
| Maximum Operating Rate | 180 cyc/min |
| Connections - Terminals | Screw Clamp terminal |
| Mounting Support | 35 mm DIN rail or plate (screw) |
| IP Degree of Protection | IP2X (front face) |
| Ambient Air Temperature for Operation | -40...60 °C (up to 70 °C with derating) |
| Dimensions (H x W x D) | 77 x 45 x 84 mm |
| Net Weight | 0.58 kg |
| Units per Package | 20 |
Certifications & Standards
- CE
- UKCA
- cULus
- CCC
- EN/IEC 60947-5-1
Selection Notes
Pick the CAD50M7 where the panel needs 5 NO switching in one block — the 50/60 Hz AC coil matches a standard control transformer secondary already present in most panels. The screw clamp wiring style is the other variant axis in this family: screw clamp terminals use a standard flat or Pozidriv screwdriver, matching existing panel wiring conventions. At 10 A Ith and a 100 A / 1 s short-time withstand, the CAD50M7 is sized for auxiliary and interlock duty alongside a main contactor, not as the load-switching device itself.