Stoklink Technical Articles

How to Read an MPCB and Contactor Coordination Table

How do you read an MPCB-contactor coordination table? A coordination table published under IEC 60947-4-1 lists, for each MPCB rated current, the exact contactor and overload relay it was tested with, the prospective short-circuit current (Icc) the combination was verified at, and whether the result was declared Type 1 or Type 2. Pick a combination outside that table — swap in a different contactor frame, exceed the tested Icc, or ignore the declared Type — and the tested coordination no longer applies, so a fault beyond the panel's design current can damage more than the manufacturer intended. This article covers the row structure, the Type 1/Type 2 column, matching rated currents, checking Icc against your installation, cross-checking the contactor and relay columns, and the mistakes that void a table's validity.

What an MPCB-Contactor Coordination Table Shows

Every MPCB manufacturer tests specific combinations of MPCB, contactor, and (where used) overload relay together in a lab, at a declared prospective short-circuit current, and publishes the results as a coordination table. The table is not a suggestion — it is the tested evidence that lets a panel builder claim compliance with IEC 60947-4-1 clause 8.2.5 without running the short-circuit test itself.

A typical row lists the MPCB type and rated current setting range, the contactor reference and its rated operational current (Ie), the overload relay reference if the MPCB is magnetic-only, the Icc value the combination was tested at, and the coordination Type achieved at that Icc. Read left to right, each row is one certified combination — not a menu where columns mix and match freely.

Coordination table is a manufacturer-published list of tested MPCB, contactor, and overload relay combinations, each with a declared short-circuit current and coordination Type, per IEC 60947-4-1 clause 8.2.5.

Type 1 vs Type 2: The Column That Decides Everything

Type 1 coordination means that after a short circuit, the MPCB and contactor may be damaged and require replacement — the fault must not endanger the operator, but the starter itself is not guaranteed serviceable. Type 2 coordination means no damage beyond light contact welding on the contactor, separable without tools, and the starter is back in service after the fault clears.

Type 2 costs more to achieve — it usually forces a lower fault-current rating for the same components, or a larger MPCB paired with the same contactor. Panels built for continuous-process lines, where an unplanned starter replacement means downtime, specify Type 2. Panels where first cost matters more than a five-minute component swap often accept Type 1. See our dedicated breakdown of MPCB Type 1 vs Type 2 coordination for the damage-tolerance details behind each declaration.

Key takeaway: Confirm which Type your specification requires before opening the table — Type 1 and Type 2 rows for the same MPCB rated current are often different combinations, not the same row with two labels.

Matching the MPCB Rated Current to the Correct Table Row

The MPCB's setting range must bracket the motor's full-load current (FLC), and the table row used must match the MPCB's rated current and dial setting — not just any row with a similar contactor. A 16 A frame set at 6 A and the same frame set at 14 A can carry different Icc ratings in the same table, because the tested fault current depends on the actual setting, not the frame alone.

Cross-reference the FLC from the motor nameplate against the MPCB's dial range first, confirm the setting sits inside that range, then find the table row for that specific rated current and setting combination. Skip a step and the coordination relied on was never tested at the operating point in use.

This is where manual motor starters from different manufacturers diverge in table structure — some group several settings under one row, others publish a row per discrete setting point. Check which format a given manufacturer uses before assuming a row applies to an exact dial position.

Reading the Icc (Short-Circuit Current) Column

Icc in the table is the prospective short-circuit current the combination was tested against, at a stated voltage (commonly 400 V or 415 V) — not the MPCB's own interrupting rating in isolation. A 65 A frame MPCB might carry a 100 kA Icu rating on its own datasheet page but only 50 kA Type 2 coordination with a specific contactor, because the contactor's let-through energy is the limiting factor, not the MPCB.

Compare the table's Icc value against the prospective fault current at the point of installation, obtained from a short-circuit study or the transformer/utility impedance data. If the fault current at that panel exceeds the table's Icc, the combination is unverified at that site, even if every individual component's own rating looks sufficient on its own datasheet.

Formula: Coordination Table Validity Check — Source: IEC 60947-4-1, clause 8.2.5

Iccapp ≤ Icctable

Symbol Description Unit
Iccapp Prospective short-circuit current at the installation point, from the fault-current study kA
Icctable Short-circuit current the MPCB/contactor combination was tested at, for the declared Type kA
In(MPCB) Rated current / dial setting of the MPCB in the table row used A
Ie(contactor) Rated operational current of the paired contactor in that row A

What we see in the field: builders sometimes read the MPCB's own Icu off its datasheet and assume that figure applies to the whole starter. It doesn't — the table's Icc is almost always lower, because it reflects the weakest component in the tested pair, not the strongest.

Key takeaway: The table's Icc is a property of the tested combination, not of any single component — a higher-Icu MPCB does not raise the coordination rating if the contactor was only tested at a lower value.

Cross-Checking the Contactor and Overload Relay Columns

For a thermal-magnetic MPCB, the table's contactor column is the only variable, since the MPCB itself provides overload protection and no separate relay row exists. For a magnetic-only MPCB, the table adds a third column: the overload relay reference, because thermal protection now lives in that separate device.

Builders using magnetic-only MPCBs sometimes size the overload relay from a generic FLC chart instead of the table's specific relay reference. The relay's trip characteristic and the magnetic-only MPCB's fixed trip point were coordinated as a pair in testing — swapping the relay brand breaks that pairing even when the new relay's current range looks compatible on paper.

Building the full starter around the exact references in one table row is the fastest way to keep the declared Type intact. See building an MPCB and contactor motor starter for the assembly side, and pair a magnetic-only MPCB with thermal overload relays only from the table's listed reference, not a generic sizing chart.

Common Mistakes When Reading Coordination Tables

Four mistakes account for most miscoordinated starters found in field audits. Reading the MPCB's standalone Icu instead of the table's tested Icc for the combination. Substituting a contactor from a different range because it shares the same Ie, without checking it appears in the same row. Using a Type 1 row when the specification calls for Type 2, because the Type 1 row often shows a higher Icc and looks like the stronger number at a glance. Ignoring the dial-setting column and applying a row validated at a different setting point to a motor with a different FLC.

This depends on how the original short-circuit study was scoped, too — a table read as valid against an older fault-current calculation may not reflect a since-expanded transformer or an added parallel feeder. Set it wrong and the coordination documented on paper does not exist on the panel.

Key takeaway: A coordination table only applies to the exact MPCB, dial setting, contactor, overload relay (if used), and Icc shown in one row — treat every substitution as unverified until the manufacturer confirms it.

How Coordination Table Format Differs by Brand

Schneider, ABB, and Siemens all publish tables that map MPCB, contactor, and Type to a declared Icc, but the layout and lookup method differ enough to slow down a first read.

Criteria Schneider TeSys ABB Siemens SIRIUS
Table format GV2/GV3/GV4 rows cross-referenced to LC1 contactor references MS116/MS132/MS165 rows cross-referenced to AF contactor references 3RV2 rows cross-referenced to 3RT2 contactor references via link modules
Setting resolution One row per discrete dial range within a frame One row per discrete dial range within a frame Frame size (S00/S0/S2/S3) grouped, setting range per row
Magnetic-only column GV2L rows show a separate overload relay reference MO132/MO165 rows show a separate overload relay reference Magnetic-only 3RV2 variants show a separate 3RU2/3RB3 relay reference
Typical declared Icc range Up to 100 kA at 400 V depending on frame and Type Up to 100 kA at 400 V depending on frame and Type Up to 100 kA at 400 V depending on frame and Type

The lookup logic stays the same across all three: find the MPCB rated current and dial setting, find the row, read the paired contactor (and relay, if magnetic-only), then read the Icc and Type for that exact row. When a project standardizes on one manufacturer's motor protection circuit breakers and contactors, staying inside that manufacturer's own table avoids cross-brand coordination questions the tables were never tested to answer.

Link module is a mechanical adaptor, used in the Siemens SIRIUS system, that mounts an MPCB directly onto a contactor, forming a compact combination whose coordination the table declares as a single tested unit.

Frequently Asked Questions

What is a Type 2 coordination table used for?

It documents that a specific MPCB, contactor, and overload relay combination, tested at a declared short-circuit current per IEC 60947-4-1, suffers no damage beyond light, separable contact welding after a fault, letting a panel builder claim compliance without independent short-circuit testing.

Can I use a different contactor than the one shown in the table row?

Not without voiding the declared coordination. The Type and Icc rating apply only to the tested combination in that row; a different contactor, even with a similar Ie, was not tested with that MPCB at that fault current.

Does a higher Icu rating on the MPCB's datasheet override the table's Icc?

No. The table's Icc reflects the tested combination's weakest link, which is often the contactor's let-through energy, not the MPCB's standalone interrupting rating.

Why do magnetic-only MPCB tables have an extra column?

A magnetic-only MPCB provides short-circuit protection only, so the table adds the specific overload relay reference it was tested with, since that relay now carries the thermal protection function.

What happens if my site's fault current exceeds the table's Icc?

The combination is unverified at that fault level. Options are selecting a higher-Icc row (larger frame or different Type), adding upstream current-limiting protection, or requesting manufacturer confirmation for the specific fault current.

Conclusion

A coordination table is read one row at a time: MPCB rated current and dial setting, paired contactor (and overload relay, if magnetic-only), declared Icc, and Type. Every substitution outside that row — a different contactor, a higher fault current, the wrong Type — needs a fresh manufacturer confirmation before it goes on the panel schedule. Start from the MPCB engineering guide for the broader selection process, and cross-check the standard itself against IEC 60947-4-1 standards for contactors and motor starters whenever a table's terminology needs clarifying.

Comments (0)

    Leave a comment