- Description
The Siemens 6SL3210-1PH26-2UL0 is a SINAMICS G120 PM240-2 power module for 3AC 500-690V supply, rated 45.00 kW at high overload and 55.00 kW at low overload in the FSE frame. It has an integrated braking chopper, no input filter, and ships without a control unit or operator panel; it is approved from CU firmware V4.7 HF8. Net weight is 27.1 kg, protection is IP20, and dimensions match the FSE frame at 551 x 275 x 237 mm.
Technical Specifications
| Order Number (MLFB) | 6SL3210-1PH26-2UL0 |
| EAN | 4042948668337 |
| Brand | Siemens |
| Series | SINAMICS G120 |
| Frame Size | FSE |
| Dimensions (H x W x D) | 551 x 275 x 237 mm |
| Country of Origin | DE |
| Number of phases | 3 AC |
| Line voltage | 500 ... 690 V ±10 % |
| Line frequency | 47 ... 63 Hz |
| Rated input current (LO) | 59.00 A |
| Rated input current (HO) | 54.00 A |
| Rated voltage | 690V IEC / 600V NEC |
| Rated power (LO) | 55.00 kW / 60.00 hp |
| Rated power (HO) | 45.00 kW / 50.00 hp |
| Rated output current (LO) | 62.00 A |
| Rated output current (HO) | 52.00 A |
| Max. output current | 104.00 A |
| Pulse frequency | 2 kHz |
| Output frequency for vector control | 0 ... 200 Hz |
| Output frequency for V/f control | 0 ... 550 Hz |
| Power loss | 1.21 kW |
| Cooling | Internal air cooling |
| Cooling air requirement | 0.083 m³/s (2.931 ft³/s) |
| Installation altitude | 1,000 m (3,280.84 ft) |
| Operation LO | -20 ... 40 °C (-4 ... 104 °F) |
| Operation HO | -20 ... 50 °C (-4 ... 122 °F) |
| Transport | -25 ... 55 °C (-13 ... 131 °F) |
| Storage | -25 ... 55 °C (-13 ... 131 °F) |
| Net weight | 27.1 kg |
Selection Notes
This is the largest FSE-frame module in this batch before the next step moves to the FSF frame at 75.00 kW low-overload; choose it over the 37.00 kW / 45.00 kW FSE variant when continuous current draw runs closer to 62.00 A than 52.00 A. Power loss of 1.21 kW is the highest figure in the FSE group, so it drives the cabinet's heat-dissipation sizing more than the frame's physical size does. The braking chopper is built in, handling occasional regeneration without an external module, though at 55 kW a dedicated braking resistor is still needed for continuous regenerative duty.