- Home
- VFD Accessories (Power Modules, Reactors, Panels)
- Siemens 6SL3210-1PE21-4UL0 SINAMICS G120 PM240-2 5.5kW 400V IP20 VFD Power Module Siemens 6SL3210-1PE21-4UL0 SINAMICS G120 PM240-2 5.5kW 400V IP20 VFD Power Module
Siemens 6SL3210-1PE21-4UL0 SINAMICS G120 PM240-2 5.5kW 400V IP20 VFD Power Module
Siemens 6SL3210-1PE21-4UL0 SINAMICS G120 PM240-2 5.5kW 400V IP20 VFD Power Module
Get Quote
- Description
The Siemens 6SL3210-1PE21-4UL0 is a SINAMICS G120 PM240-2 power module rated 5.5kW low overload (LO) / 4.0kW high overload (HO) at 380-480V 3AC, IP20, with a built-in braking chopper and no line filter fitted. It requires a separate SINAMICS control unit to run, ships without a control unit or operator panel, and supports control unit firmware version V4.6.
Technical Specifications
| SKU | 6SL3210-1PE21-4UL0 |
| Brand | Siemens |
| Series | SINAMICS G120 |
| Product designation | PM240-2 |
| Number of phases | 3 AC |
| Line voltage | 380-480 V +/-10% |
| Line frequency | 47-63 Hz |
| Rated voltage | 400V IEC / 480V NEC |
| Rated power, LO | 5.50 kW / 7.50 hp |
| Rated power, HO | 4.00 kW / 5.00 hp |
| Rated current, LO | 17.20 A |
| Rated current, HO | 15.30 A |
| Rated output current, LO | 13.20 A |
| Rated output current, HO | 10.20 A |
| Max. output current | 20.40 A |
| Overload, HO | 200% 3s, 150% 57s, 100% 240s |
| Overload, LO | 150% 3s, 110% 57s, 100% 240s |
| Pulse frequency | 4 kHz |
| Output frequency, vector control | 0-200 Hz |
| Output frequency, V/f control | 0-550 Hz |
| Power loss | 0.15 kW |
| Cooling | Internal air cooling, 0.009 m3/s |
| Frame size | FSB |
| Dimensions (H x W x D) | 291 x 100 x 165 mm |
| Degree of protection | IP20 |
| Installation altitude | 1000 m |
| Ambient temperature, operation LO | -10 to 40 degC |
| Ambient temperature, operation HO | -10 to 50 degC |
| Ambient temperature, transport/storage | -25 to 55 degC |
| Weight | 2.9 kg |
Selection Notes
The built-in braking chopper means no separate braking module is needed for dynamic braking within its capacity, which matters for overhauling loads or fast decel cycles. The HO rating (4.0kW, 200% overload for 3s) suits constant-torque loads such as conveyors that need high starting torque, while the LO rating (5.5kW, 150% overload for 3s) suits variable-torque loads like pumps and fans that run mostly at steady speed. This module ships without a line filter, so an external EMC filter is required where conducted-emission limits apply, and it needs a separate SINAMICS control unit since the power module itself has no onboard control electronics or operator interface.
Applications
Motor control for pumps, fans and conveyors in the 4-5.5kW range on modular SINAMICS G120 drive systems where a built-in braking chopper is needed without an EMC filter fitted at the power module.