- Home
- All Products
- Siemens 6ES7132-7RD01-0AB0 SIMATIC ET 200iSP 4DO 23.1V DC/20mA Ex ib Remote I/O Module Siemens 6ES7132-7RD01-0AB0 SIMATIC ET 200iSP 4DO 23.1V DC/20mA Ex ib Remote I/O Module
Siemens 6ES7132-7RD01-0AB0 SIMATIC ET 200iSP 4DO 23.1V DC/20mA Ex ib Remote I/O Module
Siemens 6ES7132-7RD01-0AB0 SIMATIC ET 200iSP 4DO 23.1V DC/20mA Ex ib Remote I/O Module
Get Quote
- Description
The Siemens 6ES7132-7RD01-0AB0 is a SIMATIC ET200iSP intrinsically safe electronic module with 4 digital outputs rated 23.1 V DC/20 mA, plus an integrated intrinsically-safe input for H shutdown. It carries ATEX and IECEx Ex ib [ia Ga] IIC T4 Gb approval for Zone 1 gas and Zone 21 dust areas, mounts on a rail or front panel, and provides screw/spring-type terminal connections with IP30 protection.
Technical Specifications
| SKU (MLFB) | 6ES7132-7RD01-0AB0 |
| Brand | Siemens |
| Series | SIMATIC ET200iSP |
| Product Type Designation | 4DQ 23.1 V DC/20 mA |
| Product Version | SHUT DOWN H |
| Number of Digital Outputs | 4, plus 1 intrinsically-safe input for H shutdown |
| Output Type | Transistor |
| No-Load Output Voltage | 23.1 V DC |
| Rated Output Current | 0.02 A |
| Current Consumption | 290 mA typ., 340 mA max with actuator supply |
| Power Loss | 2.5 W typ. |
| Cable Length | 500 m max, shielded or unshielded |
| Ex(i) Ratings | Uo 25.6 V, Io 96 mA, Po 0.61 W, Co 98 nF, Lo 3 mH (gas group IIC) |
| ATEX Marking | II 2 G Ex ib [ia Ga] IIC T4 Gb, II 2 D Ex ib [ia IIIC Da] IIC T4 Gb, I M2 Ex ib [ia] I Mb |
| Degree of Protection | IP30 |
| Connection Method | Screw/spring-type terminal |
| Dimensions (W x H x D) | 30 x 129 x 136.5 mm |
| Net Weight | 255 g |
Certifications & Standards
- GL
- ABS
- BV
- DNV
Selection Notes
The rated output is only 20 mA, so this module is sized for low-power actuators such as solenoid pilots or intrinsically-safe indicator circuits in a hazardous area, not general-purpose switching. Parallel switching of two outputs for uprating is explicitly not possible for Ex reasons, which rules out doubling current capacity the way a non-Ex module might allow. The integrated intrinsically-safe H-shutdown input is a dedicated safety-shutdown channel separate from the 4 standard DO channels, and its own Ex parameters (Ui 28 V, Pi 1.2 W, Ci 3 nF) must be checked against the connected field circuit during loop calculation.
Applications
Built for digital output signaling inside ATEX/IECEx Zone 1 gas or Zone 21 dust areas and IECEx Zone 1 marine/offshore installations, where field wiring must stay intrinsically safe, such as low-power solenoid or indicator control on process skids, tank farms, and hazardous-area production lines.