The Schneider Electric VBF5 is a 3-pole TeSys VARIO switch-disconnector rated 125 A, built from a V5 switch body and a long padlockable handle on a yellow front plate with 4-screw door mounting, for main motor switching up to 37 kW at 400 V AC-23. It carries IP65 protection once installed on the enclosure door.
Technical Specifications
| SKU | VBF5 |
| Brand | Schneider Electric |
| Range | TeSys VARIO |
| Device Short Name | VBF |
| Switch Body | V5 |
| Poles | 3P |
| Contacts | 3 NO |
| Rated Operational Voltage (Ue) | 690 V AC 50/60 Hz |
| Rated Operational Current (Ie, AC-23, 400 V) | 68.5 A |
| Conventional Free Air Thermal Current (Ith) | 125 A |
| Conventional Enclosed Thermal Current (Ithe) | 100 A |
| Rated Operational Power (AC-23A, 400-415 V) | 37 kW |
| Rated Operational Power (AC-3, 400-415 V) | 30 kW |
| Making Capacity (AC-21/22/23A, 400 V) | 1250 A |
| Breaking Capacity (AC-21/22/23A, 400 V) | 1000 A |
| Short-Circuit Making Capacity (Icm) | 2.8 kA |
| Short-Time Withstand Current (Icw, 1 s) | 1500 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Terminal Connection | 95 mm2 solid / 70 mm2 flexible with cable end |
| Tightening Torque | 22.6 N.m |
| Dimensions (H x Base) | 125 x 90 mm |
| Net Weight | 1.2 kg |
| Handle Colour / Front Plate | Black / Yellow |
| Mounting | 4-screw handle, door mounting |
| IP Degree of Protection | IP65 (mounted), IP20 (terminals) |
| Ambient Temperature (Operation) | -20 to 50 degC |
Certifications & Standards
- CCC
- UL
- CSA
- GL
- UKCA
- IEC 60947-3
Selection Notes
The VBF5 moves to a 90 x 90 mm base and 95 mm2 terminal capacity, a step up in both handle length and tightening torque (22.6 N.m) from the VBF0-VBF4 frames — plan cable gland and gland-plate clearance accordingly. Unlike the smaller VBF bodies, the V5 body only accepts two add-on poles, one per side: neutral (VZ13), earthing (VZ16) or auxiliary contacts (VZ7, VZ20); there is no separate main add-on pole for this frame.