- Home
- Schneider TeSys K Contactors
- Schneider Electric LC1K1210Q7 TeSys K Contactor 3P 3NO AC-3 12 A 1NO Aux 380-400 V AC Coil Contactor Schneider Electric LC1K1210Q7 TeSys K Contactor 3P 3NO AC-3 12 A 1NO Aux 380-400 V AC Coil Contactor
Schneider Electric LC1K1210Q7 TeSys K Contactor 3P 3NO AC-3 12 A 1NO Aux 380-400 V AC Coil Contactor
Schneider Electric LC1K1210Q7 TeSys K Contactor 3P 3NO AC-3 12 A 1NO Aux 380-400 V AC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1K1210Q7 is a 3-pole TeSys K mini contactor rated 12 A AC-3 at up to 440 V (5.5 kW at 400 V), with a 1NO built-in auxiliary contact. It runs on a 380-400 V AC 50/60 Hz coil, connects via screw clamp terminals, and fits a 45 mm DIN-rail or plate-mount footprint rated to 3600 cyc/h.
Technical Specifications
| Reference | LC1K1210Q7 |
| Brand | Schneider Electric |
| Range | TeSys K |
| GTIN | 3389110789768 |
| Device Short Name | LC1K |
| Product Type | Contactor |
| Poles | 3P, 3 NO |
| Utilisation Category | AC-3 / AC-3e |
| Rated Operational Voltage (Ue) | ≤690 V AC ≤400 Hz |
| Rated Operational Current, AC-3 (Ie) | 12 A at ≤440 V |
| Motor Power (AC-3, 380-415 V) | 5.5 kW |
| Control Circuit Voltage (Uc) | 380-400 V AC 50/60 Hz |
| Auxiliary Contact Composition | 1NO |
| Conventional Free Air Thermal Current (Ith) | 20 A (power circuit) |
| Irms Rated Making Capacity | 144 A AC |
| Rated Breaking Capacity | 110 A at 440 V |
| Rated Short-Time Withstand Current (Icw) | 115 A (1 s) / 100 A (10 s) at 50 °C |
| Associated Fuse Rating | 25 A gG (≤440 V) / 25 A aM |
| Rated Insulation Voltage (Ui) | 690 V (IEC 60947-4-1) / 600 V (UL 508, CSA C22.2 No 14) |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Connections | Screw clamp terminals |
| Mounting | DIN rail or plate |
| Maximum Operating Rate | 3600 cyc/h |
| IP Degree of Protection | IP2X |
| Dimensions (H x W x D) | 58 mm x 45 mm x 57 mm |
| Net Weight | 0.18 kg |
Certifications & Standards
- CB Scheme
- CCC
- UL
- CSA
- EAC
- CE
- UKCA
- EN/IEC 60947-4-1
- GB/T 14048.4
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
- JIS C8201-4-1
- IEC 60335-1
- IEC 60335-2-40
- UL 60335-2-40
Selection Notes
The 12 A AC-3 rating sizes this contactor for a 5.5 kW motor at 400 V; step up to a higher-current TeSys K frame, or to TeSys Deca once past 16 A, for larger motors. The 1NO auxiliary contact is fixed at the factory and cannot be field-changed, so confirm the control-circuit logic needs 1NO before ordering rather than after.