- Home
- Schneider TeSys Deca Contactors
- Schneider Electric LC1DT80AF7 TeSys Deca Contactor 4P 4NO AC-1 80 A 110 V AC Coil Contactor Schneider Electric LC1DT80AF7 TeSys Deca Contactor 4P 4NO AC-1 80 A 110 V AC Coil Contactor
Schneider Electric LC1DT80AF7 TeSys Deca Contactor 4P 4NO AC-1 80 A 110 V AC Coil Contactor
Schneider Electric LC1DT80AF7 TeSys Deca Contactor 4P 4NO AC-1 80 A 110 V AC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1DT80AF7 is a 4-pole TeSys Deca contactor rated 80 A AC-1 at up to 440 V AC, built for resistive-load switching rather than motor starting. It runs on a 110 V AC 50/60 Hz coil and ships with 1 NO + 1 NC mirror-certified auxiliary contacts built in, EverLink BTR screw connectors (power) / screw clamp terminals (control), and a 70 mm DIN-rail or plate-mount body.
Technical Specifications
| Reference | LC1DT80AF7 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| GTIN | 3389119409407 |
| Device Short Name | LC1D |
| Product Type | Contactor |
| Poles | 4P, 4 NO |
| Utilisation Category | AC-1 (resistive load) |
| Rated Operational Voltage (Ue) | ≤690 V AC 25-400 Hz / ≤300 V DC |
| Rated Operational Current (Ie) | 80 A at ≤440 V AC |
| Control Circuit Voltage (Uc) | 110 V AC 50/60 Hz |
| Conventional Free Air Thermal Current (Ith) | 80 A (power circuit) |
| Rated Breaking Capacity | 1000 A at 440 V |
| Rated Making Capacity | 1000 A at 440 V |
| Rated Short-Time Withstand Current (Icw) | 900 A (1 s) / 640 A (10 s) at 40 °C |
| Associated Fuse Rating | 125 A gG (coordination type 1) / 125 A gG (coordination type 2) |
| Auxiliary Contacts | 1 NO + 1 NC (mirror contact) |
| Rated Insulation Voltage (Ui) | 690 V (IEC 60947-4-1) |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Connections | EverLink BTR screw connectors (power) / screw clamp terminals (control) |
| Mounting | DIN rail or plate |
| IP Degree of Protection | IP20 (front face) |
| Maximum Operating Rate | 3600 cyc/h at 60 °C |
| Dimensions (H x W x D) | 122 mm x 70 mm x 120 mm |
| Net Weight | 1.15 kg |
Certifications & Standards
- UL
- CSA
- DNV
- CCC
- RINA
- BV
- LROS
- GL
- GOST
- CSA C22.2 No 14
- EN 60947-4-1
- EN 60947-5-1
- IEC 60947-4-1
- IEC 60947-5-1
- UL 60947-4-1
- IEC 60335-1
Selection Notes
The 4P/4NO contact arrangement and AC-1 rating target resistive loads — heater banks, lighting circuits — not three-phase motor AC-3 switching; pick a higher-current variant in the same range for loads above 80 A. The built-in 1 NC mirror contact lets an interlock circuit confirm all four poles are open before enabling a parallel circuit. The 110 V AC 50/60 Hz coil needs a control supply at that exact voltage, so check the panel's control transformer tap before specifying this coil code.