The Schneider Electric LC1DMKV7 is a 3-pole TeSys Deca capacitor-duty contactor rated 25 kvar at 400 V (42 kvar at 690 V) for switching three-phase power-factor-correction capacitor banks. It runs on a 400 V AC 50/60 Hz coil, includes 1 NO + 2 NC instantaneous auxiliary contacts with front-mounted early-make poles and pre-wired damping resistors, and mounts on a 45 mm wide DIN rail or plate.
Technical Specifications
| Reference | LC1DMKV7 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| GTIN | 3606480401244 |
| Device Short Name | LC1DMK |
| Product Type | Capacitor Duty Contactor |
| Poles | 3P, 3 NO |
| Contactor Application | Power factor correction |
| Utilisation Category | AC-6b |
| Rated Operational Voltage (Ue) | 690 V AC 50/60 Hz |
| Reactive Power Rating, 230 V | 14 kvar |
| Reactive Power Rating, 400 V | 25 kvar |
| Reactive Power Rating, 440 V | 27 kvar |
| Reactive Power Rating, 690 V | 42 kvar |
| Control Circuit Voltage (Uc) | 400 V AC 50/60 Hz |
| Auxiliary Contact Composition | 1 NO + 2 NC (instantaneous) |
| Device Location in System | Inside-delta interruption / line interruption |
| Connections | screw clamp terminals |
| Mounting | DIN rail or plate |
| Maximum Operating Rate | 240 cyc/h |
| IP Degree of Protection | IP20 (front face) |
| Dimensions (H x W x D) | 125 mm x 45 mm x 127 mm |
| Net Weight | 0.63 kg |
Certifications & Standards
- IECEE CB Scheme
- UKCA
- EN/IEC 60947-1
- EN/IEC 60947-4-1
- IEC 60335-1
Selection Notes
Pre-wired damping resistors on the early-make poles limit inrush current when switching capacitor banks — a feature a plain LC1D motor contactor lacks, so it should not be substituted for power-factor-correction duty. The 240 cyc/h operating-rate ceiling is set by the damping-resistor thermal limit rather than contact life, which bounds how often an automatic PFC regulator can step this stage. Choose a higher-kvar variant in the same family if the capacitor bank step exceeds 25 kvar at 400 V.