- Home
- Schneider TeSys Deca Contactors
- Schneider Electric LC1D50ABNE TeSys Deca Advanced Contactor 3P 3NO AC-3 50 A 24-60 V AC/DC Coil Contactor Schneider Electric LC1D50ABNE TeSys Deca Advanced Contactor 3P 3NO AC-3 50 A 24-60 V AC/DC Coil Contactor
Schneider Electric LC1D50ABNE TeSys Deca Advanced Contactor 3P 3NO AC-3 50 A 24-60 V AC/DC Coil Contactor
Schneider Electric LC1D50ABNE TeSys Deca Advanced Contactor 3P 3NO AC-3 50 A 24-60 V AC/DC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1D50ABNE is a TeSys Deca Advanced 3-pole (3NO) contactor rated 50 A AC-3 at up to 440 V, sized for 22 kW motors at 400 V. A wide-range 24-60 V AC/DC electronic coil takes AC or DC control signals on the same terminals, and EverLink BTR screw connectors secure the power circuit against loosening under vibration.
Technical Specifications
| Reference | LC1D50ABNE |
| Brand | Schneider Electric |
| Range | TeSys Deca Advanced |
| GTIN | 3606480988233 |
| Product Type | Contactor |
| Poles | 3P (3NO) |
| Utilisation Category | AC-1, AC-3, AC-3e, AC-4 |
| Rated Operational Voltage (Ue) | ≤ 690 V AC, 25-400 Hz |
| Rated Operational Current (Ie), AC-3, ≤440V | 50 A |
| Rated Operational Current (Ie), AC-1, ≤440V | 80 A |
| Motor Power, AC-3 at 400 V | 22 kW |
| Control Circuit Voltage (Uc) | 24-60 V AC/DC, electronic |
| Hold-In Power Consumption | 0.7 W |
| Rated Breaking Capacity at 440 V | 900 A, IEC 60947 |
| Rated Short-Time Withstand Current (Icw), 1 s | 810 A at 40 degrees C |
| Rated Insulation Voltage (Ui) | 690 V, IEC 60947-4-1 |
| Auxiliary Contact Composition | 1 NO + 1 NC, mirror contact |
| Terminal Type | EverLink BTR screw connectors (power), screw clamp (control) |
| Maximum Operating Rate | 3600 cyc/h at 60 degrees C |
| Mounting | DIN rail or screw-fixing plate |
| IP Degree of Protection | IP20, front face |
| Dimensions (H x W x D) | 122 x 55 x 120 mm |
| Net Weight | 997 g |
Certifications & Standards
- IEC 60947-4-1
- UL
- CSA
- CCC
- UKCA
Selection Notes
At 50 A AC-3 the LC1D50ABNE covers 22 kW at 400 V with 900 A breaking capacity, enough to coordinate with a 110 A upstream breaker in most panel designs. The 24-60 V AC/DC coil holds at under 1 W, so a PLC output or 24 V DC rail can drive it directly. For the same frame at different ratings, the 40 A and 65 A BNE variants share identical mounting and terminal arrangements.