- Home
- Schneider TeSys Deca Contactors
- Schneider Electric LC1D09D7 TeSys Deca Contactor 3P 3NO AC-3 9 A 42 V AC Coil Contactor Schneider Electric LC1D09D7 TeSys Deca Contactor 3P 3NO AC-3 9 A 42 V AC Coil Contactor
Schneider Electric LC1D09D7 TeSys Deca Contactor 3P 3NO AC-3 9 A 42 V AC Coil Contactor
Schneider Electric LC1D09D7 TeSys Deca Contactor 3P 3NO AC-3 9 A 42 V AC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1D09D7 is a 3-pole TeSys Deca contactor rated 9 A AC-3 (up to 440 V) for direct-on-line motor control, switching motors up to 4 kW at 400 V. It carries a 42 V AC coil, a mechanically-linked 1 NO + 1 NC auxiliary contact with mirror-contact certification, and screw-clamp terminals on both power and control circuits for DIN-rail mounting.
Technical Specifications
| Reference | LC1D09D7 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| GTIN | 3389110348712 |
| Poles | 3P |
| Pole contact composition | 3 NO |
| Utilisation category | AC-3 / AC-3e / AC-1 |
| Rated operational current (Ie), AC-3 | 9 A at ≤ 440 V AC |
| Rated operational current (Ie), AC-1 | 25 A at ≤ 440 V AC |
| Rated operational voltage (Ue) | ≤ 690 V AC 25...400 Hz |
| Motor power at 400 V (AC-3) | 4 kW |
| Control circuit voltage (Uc) | 42 V AC 50/60 Hz |
| Auxiliary contact composition | 1 NO + 1 NC (mirror contact) |
| Rated making capacity | 250 A at 440 V |
| Rated breaking capacity | 250 A at 440 V |
| Rated short-time withstand current (Icw) | 210 A - 1 s |
| IP degree of protection | IP20 (front face) |
| Mounting / terminals | rail / plate; screw clamp terminals |
| Maximum operating rate | 3600 cyc/h |
| Operating altitude | 3000 m without derating |
| Dimensions (H x W x D) | 77 x 45 x 86 mm |
| Net weight | 0.32 kg |
Certifications & Standards
- IEC 60947-4-1
- UL
- CSA
- CCC
- EAC
Selection Notes
At 9 A AC-3 it covers motors up to 4 kW at 400 V; The 42 V AC coil matches low-voltage control transformers used where reduced control-circuit voltage is a panel safety requirement. The mirror-contact-certified 1 NO + 1 NC auxiliary block confirms power-contact position for safety-circuit feedback without an external contact block.